Simplified model for thermal comfort, IAQ and energy savings in rooms conditioned by displacement ventilation aided with transient personalized ventilation

被引:35
|
作者
Al Assaad, Douaa [1 ]
Habchi, Carine [2 ]
Ghali, Kamel [1 ]
Ghaddar, Nesreen [1 ]
机构
[1] Amer Univ Beirut, Mech Engn Dept, POB 11-0236, Beirut 11072020, Lebanon
[2] Lebanese Univ, Fac Engn, Dept Mech Engn, Branch 2, Roumieh, Lebanon
关键词
Displacement ventilation; Personalized ventilation; Intermittent jet; Thermal comfort; Indoor air quality; energy savings; MOMENTUM RESPIRATORY ACTIVITIES; CROSS-CONTAMINATION; AIR-QUALITY; DESK FANS; PERFORMANCE; OFFICE; EXPOSURE; SYSTEM; FLOW; CONJUNCTION;
D O I
10.1016/j.enconman.2018.02.033
中图分类号
O414.1 [热力学];
学科分类号
摘要
The aim of this work is to evaluate the performance of an intermittent personalized ventilation (PV) system assisting a displacement ventilation (DV) system based on its ability in improving thermal comfort and protecting occupants from floor emitted passive contaminants. A simplified transient mathematical model was developed of heat and species transport to predict the temperature and concentration fields in the macroclimate room air, in the thermal plume induced by the occupant and internal heat sources and within the intermittent PV jet facing the occupant face at a fixed distance. The model's predictions of temperature and concentration were experimentally validated for a PV frequency range [0.3-1 Hz] in a climatic chamber conditioned with a DV system assisted with an intermittent PV jet. Good agreement was found between the predicted and measured values of temperature and concentration of tracer gas in the different regions of macroclimate air, thermal plume, and PV jet. The validated model was used to conduct a case study where comfort and air quality were assessed and the energy consumption of the transient PV + DV system was compared to steady PV + DV and standalone DV systems. It was found that the intermittent PV range [0.3-1 Hz] was able to improve comfort compared to steady PV and provide acceptable air quality. Moreover, energy analysis showed that the intermittent PV + DV (40 L/s) was able to achieve maximum energy savings of 54.61% and 31.58% compared to a standalone DV and steady PV respectively for equivalent comfort.
引用
收藏
页码:203 / 217
页数:15
相关论文
共 29 条
  • [1] THERMAL COMFORT AND ENERGY SAVINGS IN A SIMULATED OFFICE CONDITIONED BY A TRANSIENT PERSONALIZED VENTILATOR AND A DISPLACEMENT VENTILATION SYSTEM
    Al Assad, Douaa
    Ghali, Kamel
    Ghaddar, Nesreen
    Katramiz, Elvire
    PROCEEDINGS OF THE ASME 2020 HEAT TRANSFER SUMMER CONFERENCE (HT2020), 2020,
  • [2] THEORETICAL AND EXPERIMENTAL STUDY OF DISPLACEMENT VENTILATION SYSTEM ASSISTED BY PERSONALIZED VENTILATION: ENERGY SAVINGS AND THERMAL COMFORT
    Maichoul, A.
    Ghali, K.
    Ghaddar, N.
    23RD IIR INTERNATIONAL CONGRESS OF REFRIGERATION, 2011, 23 : 130 - 137
  • [3] Comparison of chilled ceiling and mixing ventilation assisted by intermittent personalized ventilation: Thermal comfort and energy savings
    Al Assaad D.
    Ghali K.
    Ghaddar N.
    Renewable Energy and Power Quality Journal, 2020, 18 : 431 - 436
  • [4] A simplified combined displacement and personalized ventilation model
    Alain, Makhoul
    Kamel, Ghali
    Nesreen, Ghaddar
    HVAC&R RESEARCH, 2012, 18 (04): : 737 - 749
  • [5] Simplified Model of Contaminant Dispersion in Rooms Conditioned by Chilled-Ceiling Displacement Ventilation System
    Kanaan, M.
    Ghaddar, N.
    Ghali, K.
    HVAC&R RESEARCH, 2010, 16 (06): : 765 - 783
  • [6] Evaporative cooler improves transient thermal comfort in chilled ceiling displacement ventilation conditioned space
    Ghaddar, Nesreen
    Ghali, Kamel
    Chakroun, Walid
    ENERGY AND BUILDINGS, 2013, 61 : 51 - 60
  • [7] Field study on occupant comfort and the office thermal environment in rooms with displacement ventilation
    Melikov, A
    Pitchurov, G
    Naydenov, K
    Langkilde, G
    INDOOR AIR, 2005, 15 (03) : 205 - 214
  • [8] The Energy Saving Potential and the Associated Thermal Comfort of Displacement Ventilation Systems Assisted by Personalised Ventilation
    Makhoul, Alain
    Ghali, Kamel
    Ghaddar, Nesreen
    INDOOR AND BUILT ENVIRONMENT, 2013, 22 (03) : 508 - 519
  • [9] Air quality in rooms conditioned by chilled ceiling and mixed displacement ventilation for energy saving
    Chakroun, W.
    Ghali, K.
    Ghaddar, N.
    ENERGY AND BUILDINGS, 2011, 43 (10) : 2684 - 2695
  • [10] Prediction and optimization of thermal comfort, IAQ and energy consumption of typical air-conditioned rooms based on a hybrid prediction model
    Hou, Fangli
    Ma, Jun
    Kwok, Helen H. L.
    Cheng, Jack C. P.
    BUILDING AND ENVIRONMENT, 2022, 225