Impact of phase-locked loop on small-signal dynamics of the line commutated converter-based high-voltage direct-current station

被引:49
作者
Guo, Chunyi [1 ]
Zhao, Chengyong [1 ]
Iravani, Reza [2 ]
Ding, Hui [3 ]
Wang, Xiaolin [2 ]
机构
[1] North China Elect Power Univ, State Key Lab Alternate Elect Power Syst Renewabl, Beijing 102206, Peoples R China
[2] Univ Toronto, Dept Elect & Comp Engn, Toronto, ON M5S 3G4, Canada
[3] RTDS Technol Inc, Winnipeg, MB R3T 2E1, Canada
基金
美国国家科学基金会;
关键词
HVDC power transmission; phase locked loops; voltage control; eigenvalues and eigenfunctions; time-domain analysis; commutation; HVDC power convertors; phase-locked loop; DC-side voltage controller; high-voltage direct-current inverter station system; HVDC inverter station system; line commutated converter technology; LCC technology; eigenanalysis; time-domain simulation studies; PSCAD platform; short-circuit ratio; SCR; LCC-HVDC station; oscillatory modes damping; voltage control parameters; PLL-induced instability; HVDC CONVERTER; STABILITY ANALYSIS; LCC-HVDC; VSC-HVDC; SYSTEM;
D O I
10.1049/iet-gtd.2016.1449
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This study investigates the impact of phase-locked loop (PLL) and DC-side voltage controller on small-signal dynamics of the high-voltage direct-current (HVDC) inverter station system which utilises line commutated converter (LCC) technology. The studies are conducted based on eigenanalysis of a linearised model of a study system and verified by time-domain simulation studies in the PSCAD platform. The studies show that under weak grid conditions, e.g. short-circuit ratio (SCR)=1, parameters of PLL and DC-side voltage controller of the LCC-HVDC station can highly impact the damping of the oscillatory modes and even cause instability. The studies also show that the voltage control parameters can be selected to prevent PLL-induced instability. The studies also (i) show that maximum available power and critical SCR are highly affected by PLL and DC-side voltage control and (ii) propose a procedure to systematically determine these indices.
引用
收藏
页码:1311 / 1318
页数:8
相关论文
共 18 条
[1]  
Ainsworth J. D., 1980, 3101 CIGRE, P1
[2]   PHASE-LOCKED OSCILLATOR - A NEW CONTROL SYSTEM FOR CONTROLLED STATIC CONVERTORS [J].
AINSWORTH, JD .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1968, PA87 (03) :859-+
[3]  
[Anonymous], 1991, INT C AC DC POW TRAN
[4]  
[Anonymous], C CAN C EL COMP ENG
[5]  
[Anonymous], 1997, 12041997 IEEE
[6]   Valve saturable reactor iron losses of ultrahigh-voltage direct current converter [J].
Cao, Junzheng ;
Ji, Feng ;
Liu, Jie ;
Chen, Peng .
IET SCIENCE MEASUREMENT & TECHNOLOGY, 2016, 10 (02) :77-83
[7]   Analysis of Dual-Infeed HVDC With LCC-HVDC and VSC-HVDC [J].
Guo, Chunyi ;
Zhang, Yi ;
Gole, Aniruddha M. ;
Zhao, Chengyong .
IEEE TRANSACTIONS ON POWER DELIVERY, 2012, 27 (03) :1529-1537
[8]   A COMPUTATION ALGORITHM FOR ASSESSING VOLTAGE STABILITY AT AC/DC INTERCONNECTIONS [J].
HAMMAD, AE ;
KUHN, W .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1986, 1 (01) :209-216
[9]   Phase locked loop system for FACTS [J].
Jovcic, D .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2003, 18 (03) :1116-1124
[10]   Analytical modelling of HVDC-HVAC systems [J].
Jovcic, D ;
Pahalawaththa, N ;
Zavahir, M .
IEEE TRANSACTIONS ON POWER DELIVERY, 1999, 14 (02) :506-511