A topology error identification method directly based on collinearity tests

被引:29
|
作者
Lourenco, Elizete M. [1 ]
Simoes Costa, Antonio J. A.
Clements, Kevin A.
Cernev, Rafael. A.
机构
[1] Univ Fed Parana, BR-80060000 Curitiba, Parana, Brazil
[2] Worcester Polytech Inst, Worcester, MA 01609 USA
基金
美国国家科学基金会;
关键词
bad data analysis; power system real-time operation; power system state estimation;
D O I
10.1109/TPWRS.2006.881113
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A method for topology error identification based on collinearity tests involving Lagrange multipliers and the columns of the corresponding covariance matrix is presented. It relies on a geometric interpretation of the multipliers associated with the equality constraints that model circuit breaker status in generalized state estimation. The method is conceptually simple, and its implementation requires little computational effort, therefore being suitable for real-time applications. Results of several simulated cases conducted at the substation level on a real-life test system based on a subnetwork of the Brazilian Northern power system are used to illustrate the performance of the proposed technique.
引用
收藏
页码:1920 / 1929
页数:10
相关论文
共 50 条
  • [1] A comprehensive rule based method for substation topology error identification
    Wang, Jing
    Ge, Minhui
    Sun, Hongbin
    Li, Qingxin
    Wu, Wenchuan
    Guo, Qinglai
    Zhang, Boming
    Wang, J. (jing-wang05@mails.tsinghua.edu.cn), 2012, Power System Technology Press (36): : 166 - 172
  • [2] Robust estimation method for topology error identification
    Virginia Polytechnic Inst &, State Univ, Blacksburg, United States
    IEEE Trans Power Syst, 4 (1469-1476):
  • [3] A robust estimation method for topology error identification
    Mili, L
    Steeno, G
    Dobraca, F
    French, D
    IEEE TRANSACTIONS ON POWER SYSTEMS, 1999, 14 (04) : 1469 - 1474
  • [4] A robust estimation method for topology error identification - Discussion
    Kim, H
    IEEE TRANSACTIONS ON POWER SYSTEMS, 1999, 14 (04) : 1475 - 1475
  • [5] APPROACH OF BREAKER TOPOLOGY ERROR IDENTIFICATION BASED ON POWER STATION
    Wang, Dong
    Chen, Fang
    Liang, Zhengtang
    IET Conference Proceedings, 2022, 2022 (05): : 1007 - 1014
  • [6] Method of Error Identification Based on Residual Error Data
    Li, Hui-fen
    Feng, Xiao-yong
    Hao, Sha
    2ND INTERNATIONAL CONFERENCE ON APPLIED MECHANICS, ELECTRONICS AND MECHATRONICS ENGINEERING (AMEME), 2017, : 444 - 447
  • [7] An Optimization Based Method for Topology Error Detection for State Estimation
    Sharma, Neeraj Kumar
    Chakrabarti, Saikat
    2015 IEEE INNOVATIVE SMART GRID TECHNOLOGIES - ASIA (ISGT ASIA), 2015,
  • [8] A new method of network topology error identification considering parameter and measurements errors
    Zhou X.
    Ma L.
    Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2019, 47 (09): : 128 - 135
  • [9] Improved modal truncation error in the directly analytical method for damage identification of frame structures
    Yang Youfa~1
    2.Bristol Unirereity
    Engineering Sciences, 2010, 8 (04) : 91 - 96
  • [10] Improved modal truncation error in the directly analytical method for damage identification in civil engineering
    Xu, Xiaohe
    Yang, Youfa
    Li, Shuai
    Journal of Information and Computational Science, 2015, 12 (10): : 4013 - 4020