A Fault Location Method Using Air-Gap Fluxes of Synchronous Generator

被引:2
|
作者
Matsuki, Junya [1 ]
Hayashi, Yasuhiro [2 ]
Nakano, Toshikazu
Funasaki, Yoichi
机构
[1] Univ Fukui, Dept Elect Engn, Fukui, Japan
[2] Univ Fukui, Dept Elect & Elect Engn, Fukui, Japan
关键词
transmission line fault; fault location; synchronous generator; air-gap flux; wavelet analysis;
D O I
10.1002/eej.20707
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper deals with an experimental investigation of a novel fault location method using air-gap flux distributions of a synchronous generator connected to a power system. Air-gap fluxes are the sum of field fluxes and armature reaction fluxes. Changes in armature current and In field current at a fault contribute directly to the armature reaction fluxes and field fluxes, then resultant air-gap fluxes. Therefore, air-gap fluxes can be utilized to locate a fault. Wavelet analysis is applied to the induced voltages of search coils, which are wound around a stator tooth top for measurement of the air-gap flux. It is shown that the fault type and location can be estimated based oil the change in the search coil voltages measured during the fault. (C) 2009 Wiley Periodicals, Inc. Electr Eng Jpn, 167(3): 20-27, 2009; Published online in Wiley InterScicrice (www. interscience.wiley.com). DOI 10.1002/eej.20707
引用
收藏
页码:20 / 27
页数:8
相关论文
共 50 条
  • [1] Modeling of air-gap flux inside of generator for fault location
    Matsuki, J., 1600, Institute of Electrical Engineers of Japan (132):
  • [2] Impact of Static Air-Gap Eccentricity Fault on Synchronous Generator Efficiency
    He, Yu-Ling
    Tang, Ling
    Sun, Kai
    Zhang, Wen-Hao
    Wu, Xue-Wei
    Wang, Hai-Peng
    ENERGIES, 2023, 16 (07)
  • [3] Large Synchronous Machines Diagnosis Based on Air-Gap and Stray Fluxes - An Overview
    Kedjar, Bachir
    Merkhouf, Arezki
    Al-Haddad, Kamal
    2020 INTERNATIONAL CONFERENCE ON ELECTRICAL MACHINES (ICEM), VOL 1, 2020, : 1384 - 1389
  • [4] Compositive characteristics of vibration and current of the generator air-gap eccentric fault
    Key Laboratory of Condition Monitoring and Control for Power Plant Equipment, North China Electric Power University, Baoding 071003, China
    不详
    Zhongguo Jixie Gongcheng, 2008, 3 (347-350):
  • [5] Nonlinear Modeling of Air-Gap Flux Density Distribution in a Synchronous Generator with Magnetic Saturation
    Takase, F.
    Ueda, Y.
    Denki Gakkai Ronbunshi. D, Sangyo Oyo Bumonshi/Transactions of the Institute of Electrical Engineers of Japan. D, Publication of Industry Applications Society, 116 (08):
  • [6] Calculation of pulsating losses in the air-gap of synchronous reluctance motor using finite element method
    Miljavec, D
    Jereb, P
    COMPEL-THE INTERNATIONAL JOURNAL FOR COMPUTATION AND MATHEMATICS IN ELECTRICAL AND ELECTRONIC ENGINEERING, 1995, 14 (04) : 101 - 106
  • [7] New generator air-gap measuring system
    Anon
    Diesel and Gas Turbine Worldwide, 2001, 33 (04):
  • [8] Air-Gap Eccentricity Analysis of Slow-Speed Slotless Permanent Magnet Synchronous Generator
    Kangro, Rait
    Vaimann, Toomas
    Kallaste, Ants
    Belahcen, Anouar
    2014 9TH INTERNATIONAL ELECTRIC POWER QUALITY AND SUPPLY RELIABILITY CONFERENCE (PQ 2014), 2014, : 225 - 228
  • [9] A method for dynamic simulation and detection of dynamic air-gap eccentricity in synchronous machines
    AlNuaim, NA
    Toliyat, HA
    1997 IEEE INTERNATIONAL ELECTRIC MACHINES AND DRIVES CONFERENCE RECORD, 1997, : MA251 - MA253
  • [10] Fault Detection in Variable Air-gap Resolver
    Lasjerdi, H.
    Nasiri-Gheidari, Z.
    2023 14TH POWER ELECTRONICS, DRIVE SYSTEMS, AND TECHNOLOGIES CONFERENCE, PEDSTC, 2023,