Control Strategy of Grid-connected Inverter Based on Multistage Hysteresis Regulator Under Asymmetrical Grid Conditions

被引:0
|
作者
Du Chenxi [1 ]
Du Xiaodong [2 ]
Xu Zhendong [1 ]
机构
[1] Hefei Univ Technol, Sch Elect Engn & Automat, Hefei 230009, Peoples R China
[2] Hefei Univ, Basic Teaching & Expt Dept, Hefei 230601, Peoples R China
关键词
asymmetrical grid; grid-connected inverter; multistage hysteresis regulator; CURRENT CONTROL SCHEME; VOLTAGE;
D O I
暂无
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
The effective control of a grid-connected inverter under asymmetrical grid condition is able to enhance the grid-connected operation capability of the inverter. This paper studies a control scheme of 3-phase grid-connected inverter with multistage hysteresis current regulators on the alpha beta reference frame. Under the condition of asymmetrical grid, the celerity of the multistage hysteresis is fully taken advantage of to control both positive and negative current component directly without any decomposition and grid -connected current requirements are satisfied by controlling negative sequence current of the grid to zero, suppressing active or reactive power second pulsations. Three control targets are respectively achieved through simulation.Simulation results demonstrate the effectiveness and correctness of the method.
引用
收藏
页码:8539 / 8543
页数:5
相关论文
共 50 条
  • [1] An Improved Current Control Strategy for a Grid-Connected Inverter under Distorted Grid Conditions
    Lai, Ngoc Bao
    Kim, Kyeong-Hwa
    ENERGIES, 2016, 9 (03)
  • [2] Study on control strategy of grid-connected PV inverter under unbalanced grid conditions
    Liang, H. (lianghying@163.com), 1600, Science Press (34):
  • [3] Regulator Reconstruction Strategy of Grid-Connected Inverter in Weak Grid
    Zhao, Qinglin
    Zhang, Haopu
    Song, Wenlu
    Li, Xiaoyi
    Yang, Qiuxia
    2016 IEEE 8TH INTERNATIONAL POWER ELECTRONICS AND MOTION CONTROL CONFERENCE (IPEMC-ECCE ASIA), 2016, : 451 - 457
  • [4] Research on Control Strategy of Grid-connected Inverter Under Unbalanced Voltage Conditions
    Tao, Weiqing
    Gu, Zhixia
    Wang, Leqin
    Li, Jiaxi
    2016 IEEE 8TH INTERNATIONAL POWER ELECTRONICS AND MOTION CONTROL CONFERENCE (IPEMC-ECCE ASIA), 2016,
  • [5] A Control Strategy of Grid-connected Photovoltaic Inverter under Unbalanced Voltage Conditions
    Cao, Wei
    Xu, Yonghai
    PROCEEDINGS OF 2016 17TH INTERNATIONAL CONFERENCE ON HARMONICS AND QUALITY OF POWER (ICHQP), 2016, : 209 - 213
  • [6] Analysis of control strategy for grid-connected inverter under different constraints based on asymmetric grid
    Jiang, Weidong
    Wu, Zhiqing
    Hu, Yang
    Tao, Ziran
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2015, 39 (19): : 113 - 120
  • [8] Research on the Control Method of the PV Grid-Connected Inverter under an Asymmetrical Power Grid Fault
    Tian, Shiji
    Lu, Min
    Wang, Ruikang
    Liu, Di'an
    ENERGIES, 2023, 16 (22)
  • [9] Adaptive current hysteresis control of grid-connected inverter
    Dai, Xunjiang
    Chao, Qin
    Dianli Zidonghua Shebei / Electric Power Automation Equipment, 2009, 29 (09): : 85 - 89
  • [10] A CONTROL STRATEGY FOR A SOLAR GRID-CONNECTED INVERTER
    Golbon, Navid
    Moschopoulos, Gerry
    Khajehoddin, Seyed Ali
    2013 26TH ANNUAL IEEE CANADIAN CONFERENCE ON ELECTRICAL AND COMPUTER ENGINEERING (CCECE), 2013, : 167 - 170