摘要
According to IEC60060-1, IEC60060-2 requirements, the large transformer should take impulse voltage test in site. However, this test is not performed in the field for the impulse voltage generator huge and difficult to operate. To solve this problem, IEC60060-3 propose using oscillating impulse voltage for equipment on-site impulse withstand voltage test. Oscillating impulse voltage has higher generation efficiency and close to the actual voltage waveform that electrical equipment bear. For the transformer, the oscillating impulse voltage can generated through inductive method. In order to study the generation of oscillating impulse voltage through inductive method for transformer, the simulation circuit is established using ATP soft and the oscillating switching impulse voltage characteristics is studied in this paper. The result show that the oscillating switching impulse voltage waveform that accordance with IEC requirements can be generated through inductive method for transformer.
引用
收藏
页码:169 / +
页数:2
相关论文
共 50 条
  • [1] Study on Oscillating Switching Impulse Voltage Generation for Power Transformer Onsite Test
    Liang, Jianfeng
    Zhang, Liang
    Li, Junhao
    Li, Yanming
    IEEE TRANSACTIONS ON POWER DELIVERY, 2014, 29 (05) : 2223 - 2230
  • [2] Inductive oscillating switching impulse test and partial discharge detection technology for transformer
    Li J.
    Guo F.
    Zhang L.
    Liang J.
    Zhang Z.
    Li Y.
    Li, Junhao (junhaoli@mail.xjtu.edu.cn), 2016, Science Press (42): : 1199 - 1206
  • [3] Study on Partial Discharge Characteristics of Corona Discharge in Transformer Oil under Oscillating Switching Impulse Voltage
    Liang, Jianfeng
    Zhang, Liang
    Li, Junhao
    Li, Yanming
    2013 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA (CEIDP), 2013, : 1173 - 1176
  • [4] Fault Diagnose Technology of Transformers Based on Inductive Oscillating Switching Impulse Voltage Withstand Test
    Zhang Z.
    Jin Y.
    Wu B.
    Pang P.
    Li J.
    Yang X.
    Gaodianya Jishu/High Voltage Engineering, 2019, 45 (02): : 549 - 556
  • [5] Generation of Impulse Voltage Waveforms for Tesing of UHV Transformer: A Study
    Ramarao, Gandi
    Chandrasekaran, Kandasamy
    MATERIALS TODAY-PROCEEDINGS, 2020, 24 : 1972 - 1980
  • [6] Breakdown Characteristics of Transformer Turn-insulation Under Double-exponential and Oscillating Switching Impulse Voltage
    Cao D.
    Guo R.
    Cai L.
    Jin Y.
    Hu W.
    Li J.
    Gaodianya Jishu/High Voltage Engineering, 2022, 48 (06): : 2265 - 2275
  • [7] Fault diagnosis technologies for power transformers during the on-site inductive oscillating switching impulse voltage withstand test
    Zhang, Xuanrui
    Wang, Haotian
    Guo, Ruochen
    Zhang, Zheming
    Li, Junhao
    Han, Xutao
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2022, 16 (19) : 3894 - 3905
  • [8] GENERATION OF OSCILLATING LIGHTNING IMPULSE VOLTAGE AND THEIR APPLICATION IN HIGH-VOLTAGE ENGINEERING
    GOCKENBACH, E
    MEPPELINK, J
    ETZ ARCHIV, 1983, 5 (04): : 135 - 140
  • [9] Partial Discharge Measurement and Analysis of Transformer Under Oscillating Lightning Impulse Voltage
    Zhang, Xuanrui
    Guo, Ruochen
    Yang, Yun
    Hu, Yidan
    Zhang, Zhaoyu
    Li, Junhao
    Han, Xutao
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2022, 29 (06) : 2303 - 2311
  • [10] Breakdown Characteristics of Transformer Oil in a Uniform Field under Oscillating Impulse Voltage
    Li, Junhao
    Zhang, Liang
    Jin, Yuhui
    Yao, Xiu
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2017, 24 (02) : 984 - 990