Pilot Evaluation of DSA Anode Electrochemical Scaling Applied in a Cooling Water Circulation System

被引:0
|
作者
Yu, Jian-yong [1 ]
Zhang, Gang [1 ]
Wang, Jiao-ping [1 ]
机构
[1] Univ Jinan, Sch Civil Engn & Architecture, Jinan 250022, Shandong, Peoples R China
关键词
Dimensionally Stable Anode; Current Density; Inter-electrode Distance; Specific Energy Consumption; CORROSION; CALCIUM; STEEL;
D O I
暂无
中图分类号
TP39 [计算机的应用];
学科分类号
081203 ; 0835 ;
摘要
Scale deposition in circulate cooling water system is a terrible problem which could result in the reduction of heat transfer efficiency and increasing of operational consumption. In this paper, based on the Lab scale experiment, the DSA electrodes was evaluated in cooling water scaling by pilot experiment. The experimental results indicated that, the hardness removal rate appeared approximately linear relationship with the current density, and the hardness removal rate increased rapidly with the increasing of the residence time and then tends to be stable. According to the scaling requirement and economic consumption in practical application, under the experimental condition, current density of 25.56A/m(2) and the residence time of 4min was the best working condition with the hardness removal rate of 22.87%. The research results could provide important practical basis for the development, design and commissioning of electrochemical equipment in the future.
引用
收藏
页码:186 / 190
页数:5
相关论文
共 50 条
  • [1] Lab Scale Evaluation of Circulating Cooling Water Hardness Removing Applied DSA Anode
    Wang, Jiao-ping
    Zhang, Gang
    Yu, Jian-yong
    2019 INTERNATIONAL CONFERENCE ON ENERGY, POWER, ENVIRONMENT AND COMPUTER APPLICATION (ICEPECA 2019), 2019, 334 : 196 - 201
  • [2] Pilot-scale cooling tower to evaluate corrosion, scaling, and biofouling control strategies for cooling system makeup water
    Chien, S. H.
    Hsieh, M. K.
    Li, H.
    Monnell, J.
    Dzombak, D.
    Vidic, R.
    REVIEW OF SCIENTIFIC INSTRUMENTS, 2012, 83 (02):
  • [3] Design and research on the control system of cooling water of circulation
    Chen, Hai-Xia
    Zhao, Guang-Yao
    Tang, Chuan-Ying
    Li, Hua
    Dongbei Daxue Xuebao/Journal of Northeastern University, 2008, 29 (SUPPL.): : 40 - 43
  • [4] Use of Nanosilver for Water Conditioning in Cooling Tower Circulation System
    Klosok-Bazan, Iwona
    OCHRONA SRODOWISKA, 2014, 36 (02): : 43 - 46
  • [6] Parameters of water circulation network for a district heating and cooling system
    Fu, Lin
    Pan, Jihong
    Jiang, Yi
    Journal of Hydrodynamics, 2000, 12 (01) : 87 - 95
  • [7] Studies on the properties of the sodium lignosulfonate in cooling water circulation system
    Ouyang, XP
    Qiu, XQ
    Lou, HM
    Yang, DJ
    EMERGING TECHNOLOGIES OF PULPING & PAPERMAKING, 2002, : 803 - 810
  • [8] Research on mechanisms and effects of microbial agent applied in scaling control of circulating cooling water
    Wang, Yu
    Zhang, Hanzhu
    Wang, Tianping
    Zeng, Yubin
    Ye, Chunsong
    INTERNATIONAL BIODETERIORATION & BIODEGRADATION, 2023, 185
  • [9] Pilot scale evaluation of mine water (MW) as a cooling medium
    Swart, JS
    Engelbrecht, J
    WATER SA, 2004, 30 (05) : 693 - 697
  • [10] Effective screening of scaling inhibitors for cooling water systems - Development of an accelerated electrochemical method
    Ravichandran, K
    Narayanan, TSNS
    CORROSION REVIEWS, 2002, 20 (1-2) : 105 - 113