Influence of capacitor-buffered hybrid DC circuit breaker on bipolar short circuit fault of three-terminal MMC-HVDC transmission system

被引:4
|
作者
Ding, Can [1 ]
Tian, Xiaojian [1 ]
Nie, Taiping [1 ]
Yuan, Zhao [2 ]
机构
[1] China Three Gorges Univ, Coll Elect Engn & New Energy, Yichang 443002, Peoples R China
[2] Huazhong Univ Sci & Technol, Sch Elect & Elect Engn, State Key Lab Adv Electromagnet Engn & Technol, Wuhan 430074, Peoples R China
基金
中国国家自然科学基金;
关键词
Direct-current transmission; Direct-current circuit breaker; Bipolar short circuit fault;
D O I
10.1016/j.egyr.2020.11.043
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The flexible DC transmission system needs a DC circuit breaker to remove and isolate the bipolar short-circuit fault to prevent the excessive short-circuit current from damaging the DC transmission system. In this paper, a comprehensive model of DC circuit breaker and transmission system is established by using PSCAD based on capacitive buffered hybrid DC circuit breaker. The short-circuit current waveform and DC port voltage waveform of the three-terminal +/- 350 kV flexible DC transmission system under the condition of double-pole short-circuit fault at the DC side of rectifier station are simulated and calculated. The simulation results show that the maximum current and voltage of the capacitor-buffering hybrid DC circuit breaker model is lower than that of the ideal DC circuit breaker model under the condition of bipolar short-circuit fault at the DC side of the rectifier station. The system fault waveform under different parameters of capacitor-buffered hybrid DC circuit breaker is compared and analyzed through simulation, so as to optimize the parameters of circuit breaker. It can be seen that the actual results more in line with the switching process can be obtained by using the capacitor buffer type hybrid DC circuit breaker. (C) 2020 The Authors. Published by Elsevier Ltd. This is an open access article under the CC BY-NC-ND license (http://creativecommons.org/licenses/by-nc-nd/4.0/). Peer-review under responsibility of the scientific committee of the 7th International Conference on Power and Energy Systems Engineering, CPESE 2020.
引用
收藏
页码:1276 / 1282
页数:7
相关论文
共 50 条
  • [1] Resonant DC Circuit Breaker in MMC-HVDC Transmission System
    Kinjo, Ryota
    Ohta, Ryoya
    Matayosh, Hidehito
    Senjyu, Tomonobu
    Howlader, Abdul Motin
    2017 IEEE 12TH INTERNATIONAL CONFERENCE ON POWER ELECTRONICS AND DRIVE SYSTEMS (PEDS), 2017, : 71 - 74
  • [2] Modeling and Analysis of Short-Circuit Fault Current for MMC-HVDC Grid with DC Circuit Breaker
    Jia, Haipeng
    Yin, Jingyuan
    Wei, Tongzhen
    Li, Jinke
    Wu, Lixin
    2020 6TH INTERNATIONAL CONFERENCE ON ENERGY MATERIALS AND ENVIRONMENT ENGINEERING, 2020, 508
  • [3] A Reclosing Scheme of Hybrid DC Circuit Breaker for MMC-HVdc Systems
    Zhang, Shuo
    Zou, Guibin
    Xu, Chunhua
    Sun, Weijie
    IEEE JOURNAL OF EMERGING AND SELECTED TOPICS IN POWER ELECTRONICS, 2021, 9 (06) : 7126 - 7137
  • [4] Transient fault identification method for bipolar short-circuit fault on MMC-HVDC overhead lines based on hybrid HVDC breaker
    Li, Botong
    Li, Chunbo
    Li, Bin
    Wen, Weijie
    Cui, Hanqing
    Su, Jiang
    HIGH VOLTAGE, 2021, 6 (05) : 881 - 893
  • [5] Stability Modeling of a Three-Terminal MMC-HVDC Transmission System
    Zhang, Bo
    Du, Xiong
    Du, Chengmao
    Zhao, Jingbo
    Li, Fangyuan
    IEEE TRANSACTIONS ON POWER DELIVERY, 2022, 37 (03) : 1754 - 1763
  • [6] Engineering Application of Three-terminal Hybrid DC Circuit Breaker
    Qu L.
    Yu Z.
    Chen Z.
    Zhang X.
    Chen J.
    Liu Y.
    Zeng R.
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2019, 43 (23): : 141 - 146and154
  • [7] Fast Detection Method of DC Short Circuit Fault of MMC-HVDC Grid
    Mao, Meiqin
    He, Zhuang
    Chang, Liuchen
    2019 4TH IEEE WORKSHOP ON THE ELECTRONIC GRID (EGRID), 2019, : 684 - 689
  • [8] Calculation method of nonmetallic short circuit fault current in DC side of MMC-HVDC system
    Wang Z.
    Hao L.
    Wang L.
    He J.
    Chen Z.
    Dianli Zidonghua Shebei/Electric Power Automation Equipment, 2024, 44 (03): : 187 - 194
  • [9] Practical Calculation for Bipolar Short-circuit Fault Current of Transmission Line in MMC-HVDC Grid
    Hao L.
    Li W.
    Wang Z.
    Gu Y.
    Wang G.
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2020, 44 (05): : 68 - 76
  • [10] Influence of Lightning Back-flashover Intruding Wave on DC Circuit Breaker in ±500 kV MMC-HVDC Transmission System
    Sima W.
    Si Y.
    Yang M.
    Yuan T.
    Xu W.
    Li H.
    Gaodianya Jishu/High Voltage Engineering, 2019, 45 (08): : 2375 - 2384