Fault Loop Impedance Measurement in Circuits Fed by UPS and Principle of Safety Protection

被引:2
|
作者
Katarzynski, Jacek [1 ]
Olesz, Marek [1 ]
机构
[1] Gdansk Univ Technol, Fac Elect & Control Engn, PL-80233 Gdansk, Poland
关键词
uninterruptible power supply (UPS); short-circuit; protection for safety; earth fault loop impedance measurement; UPS power supply reliability;
D O I
10.3390/su122310126
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
This paper indicates a significant problem of uncertainty of fault loop impedance (FLI) measurement in circuits powered from uninterruptible power supply (UPS) (double-conversion AC-DC-AC). The correctly determined value of this impedance, related to the short-circuit current disconnection time and to the reference value, is one of the most important elements that determines the approval of an electrical installation and its receivers for operation. To define the principles of FLI measurement, several hundred measurements of the short-circuit loop impedance in the circuits fed by the UPS, in various UPS operation modes and with various FLI instruments, were made, which allowed for the definition of measurement rules that reduce the error in assessing the effectiveness of protection against electric shock by automatic disconnection of supply. Based on the analysis of voltage and current waveforms recorded during the real short-circuit tests in the circuit fed by the UPS, a proprietary algorithm for determining the short-circuit loop impedance has been proposed.
引用
收藏
页码:1 / 17
页数:17
相关论文
共 19 条
  • [1] Influence of the fault impedance on the fault protection in inverterfed circuits with isolated neutral
    Wurm, M.
    ELEKTROTECHNIK UND INFORMATIONSTECHNIK, 2016, 133 (08): : 395 - 401
  • [2] Measurement of earth fault loop impedance in circuits with time-delay type residual current devices
    Borowski, Kornel
    Czapp, Stanislaw
    PRZEGLAD ELEKTROTECHNICZNY, 2023, 99 (02): : 289 - 292
  • [3] A NEW METHOD FOR MEASUREMENT OF EARTH FAULT LOOP IMPEDANCE
    ROSKOSZ, R
    IEEE TRANSACTIONS ON POWER DELIVERY, 1991, 6 (02) : 546 - 549
  • [4] Principle of pilot line protection based on integrated impedance of fault component
    Liu, Kai
    Suonan, Jiale
    Deng, Xuyang
    Xia, Jingde
    Wang, Li
    Jiao, Zaibin
    Dianli Zidonghua Shebei/Electric Power Automation Equipment, 2010, 30 (04): : 21 - 25
  • [5] Hardware-in-the-loop testing of impedance protection with compensation of fault impedance and DG infeed current
    Pandakov, Konstantin
    Adrah, Charles Mawutor
    Liu, Zou
    Hoidalen, Hans Kristian
    Kure, Oivind
    JOURNAL OF ENGINEERING-JOE, 2018, (15): : 1018 - 1022
  • [6] Novel principle investigation of segregated phase impedance differential protection based on fault components
    Xi'an Jiaotong University, Xi'an 710049, China
    不详
    Dianli Xitong Zidonghue, 2008, 4 (41-45+58):
  • [9] Fault Loop Impedance Measurement in High Power Photovoltaic Installation with Energy Storage
    Katarzynski, Jacek
    Olesz, Marek
    PRZEGLAD ELEKTROTECHNICZNY, 2022, 98 (03): : 25 - 27
  • [10] A Method of Earth Fault Loop Impedance Measurement without Unwanted Tripping of RCDs
    Roskosz, Ryszard
    Musial, Edward
    Czapp, Stanislaw
    2018 PROGRESS IN APPLIED ELECTRICAL ENGINEERING (PAEE), 2018,