Research on DFIG-ES System to Enhance the Fast-Frequency Response Capability of Wind Farms

被引:11
|
作者
Tu, Sijia [1 ]
Zhang, Bingda [1 ]
Jin, Xianglong [1 ]
机构
[1] Tianjin Univ, Minist Educ, Key Lab Smart Grid, Tianjin 300072, Peoples R China
基金
中国国家自然科学基金;
关键词
DFIG; ES; virtual inertia control; capacity allocation; fuzzy logic controller; POWER-CONTROL; SUPPORT;
D O I
10.3390/en12183581
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
With the increasing penetration of wind power generation, the frequency regulation burden on conventional synchronous generators has become heavier, as the rotor speed of doubly-fed induction generator (DFIG) is decoupled with the system frequency. As the frequency regulation capability of wind farms is an urgent appeal, the inertia control of DFIG has been studied by many researchers and the energy storage (ES) system has been installed in wind farms to respond to frequency deviation with doubly-fed induction generators (DFIGs). In view of the high allocation and maintenance cost of the ES system, the capacity allocation scheme of the ES system-especially for fast-frequency response-is proposed in this paper. The capacity allocation principle was to make the wind farm possess the same potential inertial energy as that of synchronous generators set with equal rated power. After the capacity of the ES system was defined, the coordinated control strategy of the DFIG-ES system with consideration of wind speed was proposed in order to improve the frequency nadir during fast-frequency response. The overall power reference of the DFIG-ES system was calculated on the basis of the frequency response characteristic of synchronous generators. In particular, once the power reference of DFIG was determined, a novel virtual inertia control method of DFIG was put forward to release rotational kinetic energy and produce power surge by means of continuously modifying the proportional coefficient of maximum power point tracking (MPPT) control. During the deceleration period, the power reference smoothly decreased with the rotor speed until it reached the MPPT curve, wherein the rotor speed could rapidly recover by virtue of wind power so that the secondary frequency drop could be avoided. Afterwards, a fuzzy logic controller (FLC) was designed to distribute output power between the DFIG and ES system according to the rotor speed of DFIG and SoC of ES; thus the scheme enabled the DFIG-ES system to respond to frequency deviation in most cases while preventing the secondary frequency drop and prolonging the service life of the DFIG-ES system. Finally, the test results, which were based on the simulation system on MATLAB/Simulink software, verified the effectiveness of the proposed control strategy by comparison with other control methods and verified the rationality of the designed fuzzy logic controller and proposed capacity allocation scheme of the ES system.
引用
收藏
页数:20
相关论文
共 42 条
  • [1] Fast-Frequency Response Provided by DFIG-Wind Turbines and its Impact on the Grid
    Ochoa, Danny
    Martinez, Sergio
    IEEE TRANSACTIONS ON POWER SYSTEMS, 2017, 32 (05) : 4002 - 4011
  • [2] Research on Coordinated Control Strategy of DFIG-ES System Based on Fuzzy Control
    Chen, Jianghong
    Yuan, Teng
    Li, Xuelian
    Li, Weiliang
    Wang, Ximu
    ENERGIES, 2023, 16 (12)
  • [3] Coordinated control strategy for the short-term frequency response of a DFIG-ES system based on wind speed zone classification and fuzzy logic control
    Peng, Bo
    Zhang, Feng
    Liang, Jun
    Ding, Lei
    Liang, Zhenglin
    Wu, Qiuwei
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2019, 107 : 363 - 378
  • [4] Fast-frequency response from wind generators - Empirical data from a Type 4 wind farm
    Rebell, Eldrich
    Rodgers, Marianne
    Stanford, David
    Fischer, Markus
    Akki, Mouhcine
    2023 IEEE POWER & ENERGY SOCIETY GENERAL MEETING, PESGM, 2023,
  • [5] Characterization of Frequency Stability in Power System with Large-Scale DFIG Wind Farms
    Munkhchuluun, Enkhtsetseg
    Meegahapola, Lasantha
    Vahidnia, Arash
    2019 IEEE INTERNATIONAL CONFERENCE ON INDUSTRIAL TECHNOLOGY (ICIT), 2019, : 601 - 606
  • [6] A New Control Strategy of DFIG-based Wind Farms for Power System Frequency Regulation
    Wang, Tongxiao
    Ding, Lei
    Yin, Shanyao
    Jiang, Jiping
    Cheng, Famin
    Si, Juncheng
    2015 IEEE PES ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2015,
  • [7] Analysis and Mitigation of Electromechanical Oscillations for DFIG Wind Turbines Involved in Fast Frequency Response
    Sun, Li
    Liu, Kai
    Hu, Jiabing
    Hou, Yunhe
    IEEE TRANSACTIONS ON POWER SYSTEMS, 2019, 34 (06) : 4547 - 4556
  • [8] Research on frequency inertia response control strategy of SCESS-DFIG system considering variable wind speed
    Sun, Dongyang
    Sun, Lizhi
    Wu, Fengjiang
    Zhang, Lei
    Geng, Wenjing
    Peng, Jing
    Liu, Fengming
    JOURNAL OF ENGINEERING-JOE, 2019, (16): : 2995 - 3001
  • [9] Optimal Allocation of Energy Storage System in DFIG Wind Farms for Frequency Support Considering Wake Effect
    Xiong, Linyun
    Yang, Shaobo
    Huang, Sunhua
    He, Donglin
    Li, Penghan
    Khan, Muhammad Waseem
    Wang, Jie
    IEEE TRANSACTIONS ON POWER SYSTEMS, 2022, 37 (03) : 2097 - 2112
  • [10] Contribution of DFIG-based wind farms to power system short-term frequency regulation
    Anaya-Lara, O
    Hughes, FM
    Jenkins, N
    Strbac, G
    IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 2006, 153 (02) : 164 - 170