Experimental and numerical study on corona onset threshold under combined AC-DC voltages in Wire-Plane electrodes

被引:5
|
作者
Ma, Ziyu [1 ]
Xia, Junyi [1 ]
He, Xuyuan [2 ]
Zhou, Yunbo [1 ]
He, Zichen [1 ]
Li, Qi [3 ]
Bian, Xingming [1 ]
机构
[1] North China Elect Power Univ, State Key Lab Alternate Elect Power Syst Renewable, Beijing 102206, Peoples R China
[2] State Grid Langfang Power Supply Co, Langfang 065000, Hebei, Peoples R China
[3] Chongqing Univ, 174 Shazheng Rd, Chongqing 400044, Peoples R China
基金
中国国家自然科学基金;
关键词
Corona discharge; Corona onset voltage; Combined AC-DC voltages; Wire-plane electrode; Space charge; ION-FLOW-FIELD; INTENSITY CHARACTERISTICS; AIR-PRESSURE; HYBRID; HUMIDITY; PERFORMANCE; DISCHARGE; PULSES; ROD;
D O I
10.1016/j.ijepes.2022.108479
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
With the large-scale application of hybrid HVDC/HVAC transmission technology, the phenomenon of corona discharge is also intensified. This paper attempts to provide a comprehensive understanding of the variation of corona onset voltage under combined AC-DC voltages. In this paper, an experimental platform for measuring corona onset voltage and current pulses of wire-plane electrode under combined AC-DC voltages was built. A new corona model of wire-plane electrode under combined AC-DC voltages was also established by using the fluid model and the ion flow field model. The corona onset voltages of wire-plane electrode under different ratios of AC and DC voltages, conductor radius and conductor spacing were measured. It turned out that the conductor radius affected the intercept of the corona onset curve, while the conductor spacing affected the slope. In addition, the type of corona only affected the intercept of the corona onset curve, not the slope. With the same fixed voltage of non-corona conductor, the corona onset voltage of the DC-side positive corona was the largest, followed by the DC-side negative corona, then was the AC-side positive half-cycle corona, and the smallest was the AC-side negative half-cycle corona. The interaction between AC voltage and DC voltage was approximately linear. The calculations of the model illustrated that the residual space charges had a blocking effect on corona discharge. Therefore, the more residual space charge was, the higher corona onset voltage would be.
引用
收藏
页数:12
相关论文
共 35 条
  • [1] Investigation of Humid Air on Corona Onset Voltage in Wire-Plane Electrodes Under AC-DC Composite Voltages via Test and Modeling
    Li, Meijun
    Ma, Ziyu
    Xia, Junyi
    Zhang, Chenxiao
    He, Xuyuan
    Zhao, Luxing
    He, Kun
    Wang, Qian
    Cheng, Li
    Bian, Xingming
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2023, 30 (03) : 1105 - 1114
  • [2] Experimental Study on Corona Onset Characteristics of Small Curvature Electrode Under Combined AC-DC Voltages
    Ma, Ziyu
    Zhou, Yunbo
    Xia, Junyi
    He, Xuyuan
    Zhao, Luxing
    Shen, Boyang
    Bian, Xingming
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2022, 29 (05) : 1785 - 1794
  • [3] Study on Corona Onset Voltage of Parallel Rod Electrodes under AC-DC Combined Voltage
    Xia, Junyi
    Qu, Jia
    Zhao, Luxing
    Bian, Xingming
    2023 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, CEIDP, 2023,
  • [4] Experiments and Analysis of Corona Inception Voltage Under Combined AC-DC Voltages at Various Air Pressure and Humidity in Rod to Plane Electrodes
    He, Zichen
    Zhu, Junyu
    Zhu, Jie
    Bian, Xingming
    Shen, Boyang
    CSEE JOURNAL OF POWER AND ENERGY SYSTEMS, 2021, 7 (04) : 875 - 888
  • [5] Experimental and Theoretical Study of Corona Inception Threshold in Rod to Plane Electrodes Under AC/DC Combined Voltage: Phase Corresponding to AC Voltage
    Xia, Junyi
    Ma, Ziyu
    He, Zichen
    He, Xuyuan
    Zhao, Luxing
    Shen, Boyang
    He, Kun
    Bian, Xingming
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2023, 30 (01) : 403 - 412
  • [6] The Role of Space Charge on Corona Inception Threshold Conditions in Rod-Plane Air Gaps at DC/AC Combined Voltages
    He, Xuyuan
    Zhou, Yunbo
    He, Zichen
    Zhu, Jie
    Zhao, Luxing
    Shen, Boyang
    Bian, Xingming
    IEEE ACCESS, 2021, 9 : 125496 - 125507
  • [7] An equivalent circuit for corona discharges caused by a point to plane arrangement at ac, dc and combined voltages
    Dezenzo, Tobias
    Betz, Thomas
    Schwarzbacher, Andreas
    2017 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENON (CEIDP), 2017, : 315 - 318
  • [8] Experimental Investigations on Partial Discharge Characteristics of Water Droplets on Polymeric Insulating Surfaces at AC, DC and Combined AC-DC Voltages
    Nazemi, M. H.
    Hinrichsen, V.
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2015, 22 (04) : 2261 - 2270
  • [9] Electric Field Distribution in Oil-pressboard Insulation under AC-DC Combined Voltages
    Qi, Bo
    Zhao, Xiaolin
    Li, Chengrong
    Wu, Hao
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2016, 23 (04) : 1935 - 1941
  • [10] Gas Generation Characteristics of Transformer oil under Combined AC-DC Voltages in the Process of Arcing
    Zhou, Y. X.
    Sha, Y. C.
    Jiang, X. X.
    Sun, Q. H.
    Wang, Y. S.
    Tian, J. H.
    2011 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, VOLS 1 AND 2, 2011, : 718 - 721