Power Oscillation Impact on Generator/Turbine Interaction for an Isolated Power System

被引:3
|
作者
Cassimere, Brandon [1 ]
Evans, B. Fred [2 ]
Martin, Donald E. [3 ]
Yang, Sheng [3 ]
机构
[1] ExxonMobil Upstream Res Co, Houston, TX 77098 USA
[2] Air Energi, Houston, TX 77072 USA
[3] ABB Inc Power Syst Consulting, Raleigh, NC 27606 USA
关键词
Compressor pulsations; isolated system; turbine/generator interactions;
D O I
10.1109/TIA.2014.2367137
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
This paper demonstrates the impact power oscillations have on the turbines/generators on an isolated power system from large synchronous motor-driven compressors. This paper describes the isolated system and the methods used to model the electrical and mechanical system. The system models the mechanical compressors with torque pulses, which are translated into the electrical system as current pulsations, and then through the generators and onto the generator/turbine mechanical system as power oscillations. These oscillations can impact the shaft torsional modes of the turbines/generators and this impact is detailed in this paper. The key to this evaluation was the integration of the electrical synchronous machine models with the mechanical system models. The validity of the turbine torsional model was critical and was checked against the manufacturer's model used for the turbine design. This paper reviews various options to mitigate the impact of the power oscillations and compares the effectiveness of each option. Several operating modes are evaluated for the oscillation frequency and magnitude of torque and power impact on each generator/turbine. The results of each mitigating option and various operating modes are detailed in this paper.
引用
收藏
页码:2657 / 2664
页数:8
相关论文
共 50 条
  • [1] POWER OSCILLATION IMPACT ON GENERATOR/TURBINE INTERACTION FOR AN ISOLATED POWER SYSTEM
    Cassimere, Brandon
    Martin, Don E.
    Evans, B. Fred
    Yang, Sheng
    2014 IEEE PETROLEUM AND CHEMICAL INDUSTRY TECHNICAL CONFERENCE (PCIC), 2014,
  • [2] WIND TURBINE GENERATOR INTERACTION WITH DIESEL GENERATORS ON AN ISOLATED POWER SYSTEM
    SCOTT, GW
    WILREKER, VF
    SHALTENS, RK
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1984, 103 (05): : 933 - 937
  • [3] Influence of Constant Speed Wind Turbine Generator on Power System Oscillation
    Thakur, Devbratta
    Mithulananthan, Nadarajah
    ELECTRIC POWER COMPONENTS AND SYSTEMS, 2009, 37 (05) : 478 - 494
  • [4] Instability and dynamics of a wind turbine generator system on an isolated power system
    Das, D.
    Kothari, D.P.
    Journal of the Institution of Engineers (India): Electrical Engineering Division, 1995, 76 : 69 - 71
  • [5] Analysis on Isolated Power System Oscillation Mode and Verification of Generator Speed Governor Parameters
    Zheng Wei
    Bai Runqing
    Hao Ruhai
    PROCEEDINGS OF 2016 IEEE ADVANCED INFORMATION MANAGEMENT, COMMUNICATES, ELECTRONIC AND AUTOMATION CONTROL CONFERENCE (IMCEC 2016), 2016, : 1302 - 1305
  • [6] Frequency Drift of Sub-Synchronous Oscillation in Wind Turbine Generator Integrated Power System
    Wang Y.
    Du W.
    Wang H.
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2020, 35 (01): : 146 - 157
  • [7] Power variations of a wind turbine generator connecting to power system.
    Kodama, N
    Matsuzaka, T
    Inomata, N
    SICE 2002: PROCEEDINGS OF THE 41ST SICE ANNUAL CONFERENCE, VOLS 1-5, 2002, : 3177 - 3182
  • [8] Inter-Area Power Oscillation Frequency Mode with Wind Turbine Generator in Irish Power System using PMU Data
    Iswadi, H. R.
    Best, R. J.
    Morrow, D. J.
    2013 48TH INTERNATIONAL UNIVERSITIES' POWER ENGINEERING CONFERENCE (UPEC), 2013,
  • [9] The Impact of Hydro-Turbine and its Governor System on Power System Low Frequency Oscillation
    Zhu, Jian-Guo
    ADVANCES IN POWER AND ELECTRICAL ENGINEERING, PTS 1 AND 2, 2013, 614-615 : 875 - 879
  • [10] Power Conditioner for Stabilizing Power Disturbance caused of Wind Turbine Generator System
    Saga, Yasunao
    Fujii, Kansuke
    Yoda, Kazuyuki
    2014 INTERNATIONAL POWER ELECTRONICS CONFERENCE (IPEC-HIROSHIMA 2014 - ECCE-ASIA), 2014, : 1748 - 1752