Harmonic elimination, voltage control and load balancing in an isolated power generation

被引:0
|
作者
Kasal, Gaurav Kumar [1 ]
Singh, Bhim [1 ]
机构
[1] Indian Inst Technol, Dept Elect Engn, New Delhi 110016, India
来源
关键词
standalone asynchronous generator; power quality; voltage control; load balancing; harmonic elimination; INDUCTION GENERATOR; REGULATOR; STATCOM;
D O I
10.1002/etep.358
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper deals with an implementation of a voltage controller for an isolated power generating system employing an asynchronous generator. In such standalone system, an asynchronous generator is driven by a constant speed prime mover such as diesel, bio-gas and a gasoline engine etc. and it is isolated from the grid. A three-phase insulated gate bipolar junction transistor (IGBT) based current controlled voltage source converter (CC-VSC) with a dc bus capacitor is used to regulate the magnitude of the generated voltage along-with its functioning as a harmonic eliminator and a load balancer. The proposed controller for an isolated generating system is developed using dSPACE-DS1104 DSP controller and extensive tests are conducted with non-linear and unbalanced loads to demonstrate its capability. Copyright (C) 2009 John Wiley & Sons, Ltd.