A new site selection method applied to Synchronous condenser's suppressing transient over-voltage at the sending end of new energy resources

被引:0
|
作者
Zhao, Mengyang [1 ]
Tang, Xiaobo [1 ]
Wang, Yu [2 ]
Wang, Qilun [1 ]
Sun, Zhongqing [2 ]
机构
[1] Nanjing Normal Univ, Nanjing 210042, Peoples R China
[2] NARI Grp Corp, State Grid Elect Power Res Inst, Nanjing 211106, Peoples R China
关键词
D O I
10.1088/1755-1315/632/4/042013
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
The transient over-voltage will occur in the wind farm near the DC system after commutation failure. In order to reduce the transient over-voltage of wind power plant after the accident of off - grid, improve the stability of the system. This paper mainly studies the placement of the Synchronous condenser in the wind power station. Firstly, the advantages of the Synchronous condenser are analyzed theoretically, and the operation characteristics of the Synchronous condenser under the fault of the DC system are analyzed in detail. Secondly, based on the transient over-voltage area method, a transient over-voltage degree index is proposed, and this index is used as the optimal placement method. Finally, the proposed transient over-voltage index was verified in the PSD-BPA model. The results show that the index is correct and effective in determining the placement point of the Synchronous condenser in the new energy supply.
引用
收藏
页数:10
相关论文
共 4 条
  • [1] Impact of new-type synchronous condenser on voltage stability of jarud sending-end system
    Wu, Meng
    Dong, Zhiwei
    Li, Pengli
    Ma, Xintong
    Jin, Zikai
    Zhu, Sitong
    Cai, Yupeng
    2018 INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY (POWERCON), 2018, : 2654 - 2659
  • [2] Optimal Configuration Strategy of Distributed Synchronous Condenser for Large-scale New Energy Sending End System
    Zhang, Aijun
    Jin, Xin
    Li, Dandan
    Xu, Guorui
    2024 7TH ASIA CONFERENCE ON ENERGY AND ELECTRICAL ENGINEERING, ACEEE 2024, 2024, : 312 - 316
  • [3] Synchronous Condenser Site Selecting Method for Reducing the Trip-off Risk of New Energy Generators
    Wang, Yu
    Liu, Fusuo
    Li, Haifeng
    Wu, Xuelian
    Hou, Yuqiang
    Zhao, Xuemao
    PROCEEDINGS OF 2019 INTERNATIONAL FORUM ON SMART GRID PROTECTION AND CONTROL (PURPLE MOUNTAIN FORUM), VOL I, 2020, 584 : 75 - 83
  • [4] A Fast Screening Method for the High-Risk Faults with Transient Voltage Instability in Receiving-End Power Grids Interconnected with New Energy
    Yang, Jinzhou
    Li, Yecheng
    Xiong, Hongtao
    Kong, He
    Xue, Ancheng
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2024, 39 (21): : 6746 - 6758