Arcing Faults in Electrical Equipment

被引:6
|
作者
Sweeting, David [1 ]
机构
[1] Sweeting Consulting, St Ives, NSW 2075, Australia
关键词
Arc discharges; arc flash; arcing fault; constricted column; diffuse plasma; electrocution; electrode jets; energy transfer; line-radiation emission; plasma cloud; plasma generation; radiation absorption; ventricular fibrillation;
D O I
10.1109/TIA.2010.2091476
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
Electrical incidents that result in significant injuries to people are often the result of substantially unconstrained free-burning arcing-fault currents within electrical equipment. It is necessary to understand the nature of these arcs and be able to quantify the parameters before it is possible to really comprehend what is actually happening inside arcing faults and how they cause injuries to personnel in the immediate vicinity. This requires an understanding of the energy dissipation and the energy transfers in the vicinity of these uncontrolled arcs. This paper sets out to describe the physics of arcing faults and uses this to describe the energy transfers within an arcing fault. This provides a basis for describing the potential energy transfers to personnel in the vicinity of an arcing fault. This includes arc-root movements on humans and the transfer of the arc out of the body, which occurs in milliseconds. This has a significant impact on ventricular fibrillation and personal protective equipment for high-voltage workers.
引用
收藏
页码:387 / 397
页数:11
相关论文
共 50 条
  • [1] ARCING FAULTS IN ELECTRICAL EQUIPMENT
    Sweeting, David
    INDUSTRY APPLICATIONS SOCIETY 56TH ANNUAL PETROLEUM AND CHEMICAL INDUSTRY CONFERENCE, 2009, : 1 - 11
  • [2] Energy transfers within arcing faults in electrical equipment
    Sweeting, David
    Stokes, A. D.
    ICEFA 2007: EIGHTH INTERNATIONAL CONFERENCE ON ELECTRIC FUSES AND THEIR APPLICATIONS, PROCEEDINGS, 2007, : 169 - 178
  • [3] EXPLOSIONS DUE TO FAULTS IN ELECTRICAL EQUIPMENT
    NETTLETON, MA
    ELECTRICAL REVIEW, 1975, 197 (04): : 116 - 119
  • [4] The Analysis of Marine Electrical Equipment Common Faults
    Yuan Renmin
    PROCEEDINGS OF THE FIRST INTERNATIONAL CONFERENCE ON INFORMATION SCIENCES, MACHINERY, MATERIALS AND ENERGY (ICISMME 2015), 2015, 126 : 289 - 292
  • [5] Prevention of Oil-Immersed Equipment Rupture Due to Arcing Faults Based on Metal Foam
    Yan, Chenguang
    Guo, Jiaxu
    Zhang, Peng
    Liu, Hao
    Zhang, Baohui
    IEEE TRANSACTIONS ON POWER DELIVERY, 2023, 38 (04) : 2965 - 2968
  • [6] Vibration monitoring for diagnosis of electrical equipment's faults
    Iorgulescu, Mariana
    Beloiu, Robert
    Popescu, Mihai Octavian
    OPTIM 2010: PROCEEDINGS OF THE 12TH INTERNATIONAL CONFERENCE ON OPTIMIZATION OF ELECTRICAL AND ELECTRONIC EQUIPMENT, PTS I-IV, 2010, : 493 - +
  • [7] Radiometric Detection and Analysis of Arcing Faults
    Harris, Rachel M.
    Judd, Martin D.
    Moore, Philip J.
    Livie, James
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2015, 22 (03) : 1547 - 1558
  • [8] Recognition of arcing faults on transmission lines
    Kostyla, Pawel
    Lobos, Tadeusz
    Jaroszewski, Maciej
    PRZEGLAD ELEKTROTECHNICZNY, 2008, 84 (10): : 174 - 177
  • [9] Detection and location of low-level arcing faults in metal-clad electrical apparatus
    Sidhu, TS
    Sachdev, MS
    Sagoo, GS
    SEVENTH INTERNATIONAL CONFERENCE ON DEVELOPMENTS IN POWER SYSTEM PROTECTION, 2001, (479): : 157 - 160
  • [10] Thermochromic insulation composites for prewarning of thermal faults in electrical equipment
    Jiang, Xianrui
    Hu, Tianyu
    Yao, Ke
    Xiong, Ruotong
    Qu, Jiashu
    Liu, Qichang
    Niu, Chaolu
    Sun, Potao
    Sima, Wenxia
    JOURNAL OF APPLIED POLYMER SCIENCE, 2025, 142 (04)