Second-law-based thermodynamic analysis of two-stage and mechanical-subcooling refrigeration cycles

被引:64
|
作者
Zubair, SM
Yaqub, M
Khan, SH
机构
[1] Department of Mechanical Engineering, King Fahd Univ. Petrol. and Minerals
关键词
refrigerating cycle; compression; two-stage cycle; thermodynamics; sub-cooling; performance; H134a; R22;
D O I
10.1016/S0140-7007(96)00045-X
中图分类号
O414.1 [热力学];
学科分类号
摘要
Thermodynamic analysis of HFC-134a vapor-compression refrigeration cycles is investigated by both the first and second laws of thermodynamics. Second-law analysis is carried out for both two-stage and mechanical-subcooling refrigeration cycles. The analysis is performed on each of the system components to determine their individual contribution to the overall system irreversible losses. It is found that most of the losses are due to a low compressor efficiency. Irreversibilities of expansion valves and condenser are also significant. In addition, it is shown that the optimum inter-stage pressure for two-stage and mechanical-subcooling refrigeration systems is very close to the saturation pressure corresponding to the arithmetic mean of the refrigerant condensation and evaporation temperatures. These results are compared with the existing practice in the industry. Furthermore, theoretical results of a two-stage refrigeration system performance are also compared with experimental values for a CFC-22 system. Copyright (C) 1996 Elsevier Science Ltd and IIR
引用
收藏
页码:506 / 516
页数:11
相关论文
共 50 条
  • [1] ON OPTIMUM INTERSTAGE PRESSURE FOR 2-STAGE AND MECHANICAL-SUBCOOLING VAPOR-COMPRESSION REFRIGERATION CYCLES
    ZUBAIR, SM
    KHAN, SH
    JOURNAL OF SOLAR ENERGY ENGINEERING-TRANSACTIONS OF THE ASME, 1995, 117 (01): : 64 - 66
  • [2] Performance analysis of two-stage CO2 transcritical refrigeration cycles with absorption subcooling and mechanical recooling
    Huang, Caoxuheng
    Li, Zeyu
    Ye, Zhihao
    Wang, Ruiting
    INTERNATIONAL JOURNAL OF REFRIGERATION, 2023, 153 : 33 - 47
  • [3] Second-law analysis of two-stage vapour compression refrigeration plants
    Torrella, E.
    Llopis, R.
    Cabello, R.
    Sanchez, D.
    Larumbe, J. A.
    INTERNATIONAL JOURNAL OF EXERGY, 2010, 7 (06) : 641 - 653
  • [4] SECOND LAW BASED THERMODYNAMIC ANALYSIS OF COMPRESSION-ABSORPTION CASCADE REFRIGERATION CYCLES
    Cimsit, Canan
    Ozturk, Ilhan Tekin
    Hosoz, Murat
    ISI BILIMI VE TEKNIGI DERGISI-JOURNAL OF THERMAL SCIENCE AND TECHNOLOGY, 2014, 34 (02) : 9 - 18
  • [6] Performance analysis of two-stage compression transcritical CO2 refrigeration system with 8290 mechanical subcooling unit
    Liu, Shengchun
    Lu, Fenping
    Dai, Baomin
    Nian, Victor
    Li, Hailong
    Qi, Haifeng
    Li, Jiayu
    ENERGY, 2019, 189
  • [7] Two-stage refrigeration for subcooling liquid hydrogen and oxygen as densified propellants
    Baik, JH
    Chang, HM
    Notardonato, W
    Cryocoolers 13, 2005, : 711 - 718
  • [8] Second-law-based analysis of vapor-compression refrigeration cycles: Analytical equations for COP and new insights into features of refrigerants
    Ma, Weiwu
    Fang, Song
    Su, Bo
    Xue, Xinpei
    Li, Min
    ENERGY CONVERSION AND MANAGEMENT, 2017, 138 : 426 - 434
  • [9] Thermodynamic analysis of subcooling and superheating effects of alternative refrigerants for vapour compression refrigeration cycles
    Sencan, A
    Selbas, R
    Kizilkan, Ö
    Kalogirou, SA
    INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2006, 30 (05) : 323 - 347
  • [10] Thermodynamic analysis of two-stage and dual-temperature ejector refrigeration cycles driven by the waste heat of exhaust gas
    Liang, Youcai
    Ye, Kai
    Zhu, Yan
    Lu, Jidong
    ENERGY, 2023, 278