Why Can't I Start My Motor: Lessons Learned from Bad Motor Protective Settings

被引:0
|
作者
Smith, Terrence [1 ]
Yogaratnam, Jeyanth [1 ]
Ernst, Thomas [1 ]
机构
[1] GE Digital Energy, Atlanta, GA 30339 USA
关键词
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Motor management relays can enhance protection by locking out a motor after a trip or a stop until the motor has cooled enough to restart the motor. This feature enhances motor protection because it insures the start will not cause the motor temperature to exceed the thermal damage curve. As with any protective relay setting, correct settings are important, but with restart protection they can be particularly difficult due to the fact that they prevent restart of the process that is driven by the motor. Topics to be discussed in this paper include: motor hot cold ratio, RTD biasing, learned motor starting data, motor starting margins, running cool time constant and stopped cool time constant. Each of these values will be discussed in detail and will be shown with a case study that unnecessarily prevented restart of motor.