Incorporation of voltage stability operating limits in composite system adequacy assessment: BC hydro's experience

被引:8
|
作者
Li, W [1 ]
Mansour, Y [1 ]
Vaahedi, E [1 ]
Pettet, DN [1 ]
机构
[1] BC Hydro, Grid Operat & Interutil Affairs, Vancouver, BC, Canada
关键词
voltage stability operating limits; composite system adequacy assessment; linear programming;
D O I
10.1109/59.736265
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents an approach for incorporating actual voltage stability operating limits (VSOL) in the composite system adequacy evaluation. The VSOL curves are fitted into simplex-type straight lines and added in the linear programming model for minimizing load curtailment as additional constraints. The incorporated voltage stability limits are those calculated for the operators in the System Control Center. The introduction of the actual limits therefore leads to adequacy evaluation closer to the operation reality with very little overhead since the voltage stability operating limits are pre-calculated for system operation. The case studies for BC Hydro's 500/230 kV system are given and discussed.
引用
收藏
页码:1279 / 1284
页数:6
相关论文