Class B Fire-Extinguishing Performance Evaluation of a Compressed Air Foam System at Different Air-to-Aqueous Foam Solution Mixing Ratios

被引:20
|
作者
Rie, Dong-Ho [1 ]
Lee, Jang-Won [2 ]
Kim, Seonwoong [3 ]
机构
[1] Incheon Natl Univ, Fire Disaster Protect Res Ctr, Inchon 22012, South Korea
[2] Incheon Natl Univ, Dept Safety Engn, Inchon 22012, South Korea
[3] Youngsan Univ, Dept Architecture & Plant Engn, 288 Junam Ro, Yangsan Si 50510, Kyungsangnam Do, South Korea
来源
APPLIED SCIENCES-BASEL | 2016年 / 6卷 / 07期
关键词
compressed air foam system; experiment; fire model; air-to-aqueous foam solution; mixing ratio; fire-extinguishing performance evaluation;
D O I
10.3390/app6070191
中图分类号
O6 [化学];
学科分类号
0703 ;
摘要
The purpose of this research is to evaluate the fire-extinguishing performance of a compressed air foam system at different mixing ratios of pressurized air. In this system, compressed air is injected into an aqueous solution of foam and then discharged. The experimental device uses an exclusive fire-extinguishing technology with compressed air foam that is produced based on the Canada National Laboratory and UL (Underwriters Laboratories) 162 standards, with a 20-unit oil fire model (Class B) applied as the fire extinguisher. Compressed air is injected through the air mixture, and results with different air-to-aqueous solution foam ratios of 1:4, 1:7, and 1:10 are studied. In addition, comparison experiments between synthetic surfactant foam and a foam type which forms an aqueous film are carried out at an air-to-aqueous solution foam ratio of 1:4. From the experimental results, at identical discharging flows, it was found that the fire-extinguishing effect of the aqueous film-forming foam is greatest at an air-to-aqueous solution foam ratio of 1:7 and weakest at 1:10. Moreover, the fire-extinguishing effect of the aqueous film-forming foam in the comparison experiments between the aqueous film-forming foam and the synthetic surfactant foam is greatest.
引用
收藏
页数:12
相关论文
共 25 条
  • [1] Extinguishing efficiency of pool fire with compressed air foam
    Lin, Lin
    Zhang, Yong-Feng
    Zhang, Yu
    Weng, Tao
    Fang, Yu-Dong
    Liao, Guang-Xuan
    Ranshao Kexue Yu Jishu/Journal of Combustion Science and Technology, 2008, 14 (02): : 176 - 180
  • [2] The feasibility study of extinguishing oil tank fire by using compressed air foam system
    Zhao, Hao
    Liu, Jin-shuo
    2015 INTERNATIONAL CONFERENCE ON PERFORMANCE-BASED FIRE AND FIRE PROTECTION ENGINEERING (ICPFFPE 2015), 2016, 135 : 61 - 66
  • [3] Fire-extinguishing performance and mechanism of aqueous film-forming foam in diesel pool fire
    Xu, Zhisheng
    Guo, Xing
    Yan, Long
    Kang, Wendong
    CASE STUDIES IN THERMAL ENGINEERING, 2020, 17
  • [4] Application of compressed air foam system in extinguishing oil tank fire and middle layer effect
    Fu Xuecheng
    Bao Zhiming
    Chen Tao
    Xia Jianjun
    Zhang Xianzhong
    Zhang Jin
    Hu Yingnian
    2012 INTERNATIONAL SYMPOSIUM ON SAFETY SCIENCE AND TECHNOLOGY, 2012, 45 : 669 - 673
  • [5] An effective compressed air foam fire suppression system
    Kim, AK
    PROGRESS IN SAFETY SCIENCE AND TECHNOLOGY, 1998, : 657 - 667
  • [6] Research on Key Parameters and Fire Extinguishing Effectiveness of Compressed Air Foam System Used for UHV Substation
    Zhang, Jiaqing
    Shang, Fengju
    Zhang, Shanwen
    Wang, Liufang
    Ke, Yanguo
    Huang, Jie
    Su, Wen
    Liu, Rui
    Sheng, Youjie
    FIRE TECHNOLOGY, 2024,
  • [7] Fire-extinguishing performance and gas-phase pollution characteristics of different foam agents in extinguishing transformer oil pool fire
    Zhang, Jiaqing
    Shang, Fengju
    Zhou, Wencheng
    Xiao, Fei
    Cheng, Dengfeng
    JOURNAL OF FIRE SCIENCES, 2022, 40 (06) : 463 - 478
  • [9] Experimental study on fire extinguishing with a newly prepared multi-component compressed air foam
    WANG XiShi LIAO YaoJian LIN Lin State Key Laboratory of Fire Science University of Science and Technology of China Hefei China
    Chinese Science Bulletin, 2009, 54 (03) : 492 - 496
  • [10] Experimental study on fire extinguishing with a newly prepared multi-component compressed air foam
    Wang Xishi
    Liao YaoJian
    Lin Lin
    CHINESE SCIENCE BULLETIN, 2009, 54 (03): : 492 - 496