Effect of electronic anti-fouling treatment on fouling mitigation with circulating cooling-tower water

被引:10
|
作者
Kim, WT [1 ]
Cho, YI [1 ]
Bai, C [1 ]
机构
[1] Drexel Univ, Dept Mech Engn & Mech, Philadelphia, PA 19104 USA
关键词
D O I
暂无
中图分类号
O414.1 [热力学];
学科分类号
摘要
The purpose of the present study was to investigate the effect of electronic antifouling (EAF) technology on fouling mitigation in a heat exchanger in an open, cooling-tower system. Two tests were performed in a rectangular heat-transfer channel at 5 cycles of concentration: one without the EAF treatment and the other with the EAF treatment. The fouling resistance in the case with the EAF treatment was about 70% less than that in the case without the EAF treatment at the end of 270-hr tests. (C) 2001 Elsevier Science Ltd.