Improved Power Transformer Winding Fault Detection using FRA Diagnostics - Part 1: Axial Displacement Simulation

被引:110
|
作者
Hashemnia, Naser [1 ]
Abu-Siada, A. [1 ]
Islam, S. [1 ]
机构
[1] Curtin Univ, Perth, WA 6845, Australia
关键词
Power transformer; condition monitoring; FRA; axial faults; insulator winding integrity diagnostics; SHORT-CIRCUIT; LEAKAGE-FLUX; MOVEMENT; SUPPORT; FORCE; MODEL;
D O I
10.1109/TDEI.2014.004591
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Frequency response analysis (FRA) has become a widely accepted tool to detect power transformer winding deformation due to the development of FRA test equipment. Because FRA relies on graphical analysis, interpretation of its signature is a very specialized area that calls for skilled personnel, as so far, there is no reliable standard code for FRA signature identification and quantification. Many researchers investigated the impact of various mechanical winding deformations on the transformer FRA signature using simulation analysis by altering particular electrical parameters of the transformer equivalent electrical circuit. None of them however, investigated the impact of various physical fault levels on the corresponding change in the equivalent circuit parameters. In this paper, the physical geometrical dimension of a single-phase transformer is simulated using 3D finite element analysis to emulate the real transformer operation. A physical axial displacement of different fault levels is simulated in both low voltage and high voltage windings. The impact of each fault level on the electrical parameters of the equivalent circuit is investigated. A key contribution of this paper is the charts it introduces to correlate various axial displacement levels with the percentage change of all transformer equivalent circuit parameters due to the axial displacement fault. In contrary with other researchers who only considered mutual inductance between low voltage and high voltage windings, simulation results shown in this paper reveal that other circuit parameters should be changed by a particular percentage to accurately simulate particular fault level of transformer winding axial displacement. Results of this paper aid to precisely simulating winding axial displacement using transformer equivalent circuit that facilitates accurate qualitative and quantitative analysis of transformer FRA signatures.
引用
收藏
页码:556 / 563
页数:8
相关论文
共 50 条
  • [1] Improved Power Transformer Winding Fault Detection using FRA Diagnostics - Part 2: Radial Deformation Simulation
    Hashemnia, Naser
    Abu-Siada, A.
    Islam, S.
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2015, 22 (01) : 564 - 570
  • [2] FRA lookup charts for the quantitative determination of winding axial displacement fault in power transformers
    Tahir, Mehran
    Tenbohlen, Stefan
    IET ELECTRIC POWER APPLICATIONS, 2020, 14 (12) : 2370 - 2377
  • [3] Impact of Axial Displacement on Power Transformer FRA Signature
    Hashemnia, Naser
    Abu-Siada, A.
    Islam, S.
    2013 IEEE POWER AND ENERGY SOCIETY GENERAL MEETING (PES), 2013,
  • [4] Improved detection of power transformer winding movement by extending the FRA high frequency range
    Wang, M
    Vandermaar, AJ
    Srivastava, KD
    IEEE TRANSACTIONS ON POWER DELIVERY, 2005, 20 (03) : 1930 - 1938
  • [5] Detection of Power Transformer Winding Deformation Using Improved FRA Based on Binary Morphology and Extreme Point Variation
    Zhao, Zhongyong
    Yao, Chenguo
    Li, Chengxiang
    Islam, Syed
    IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2018, 65 (04) : 3509 - 3519
  • [6] Fault Identification for Transformer Axial Winding Displacement Using Nanosecond IFRA and SFRA Experiments
    Huang, J. J.
    Tang, W. H.
    Xin, Y. L.
    Zhou, J. J.
    Wu, Q. H.
    2018 3RD ASIA CONFERENCE ON POWER AND ELECTRICAL ENGINEERING (ACPEE 2018), 2018, 366
  • [7] Fault Diagnosis of Autotransformer Winding Axial Displacement Using FRA Method Based on Dynamic Frequency Division
    Guo L.
    Jiang F.
    Yu X.
    Wang D.
    Zhou L.
    Lin T.
    Zhongguo Tiedao Kexue/China Railway Science, 2022, 43 (01): : 134 - 143
  • [8] Detection for Axial Displacement Fault of Winding in Autotransformer Based on Dynamic Frequency Division of FRA and HHO-RF
    Zhou, Lijun
    Zang, Jialei
    Zhao, Chen
    Qian, Guochao
    Fu, Anzhi
    Wang, Dongyang
    Guo, Lei
    Jiang, Feiming
    IEEE SENSORS JOURNAL, 2024, 24 (20) : 32619 - 32629
  • [9] Recognition of power transformer winding movement and deformation using FRA
    Saied, Mohamed M.
    Al-Shaher, Meshal A.
    COMPEL-THE INTERNATIONAL JOURNAL FOR COMPUTATION AND MATHEMATICS IN ELECTRICAL AND ELECTRONIC ENGINEERING, 2007, 26 (05) : 1392 - 1410
  • [10] Partial discharge detection in transformer winding using FRA analysis
    Aissaoui, Nassima
    Houassine, Hamza
    Kabache, Nadir
    PRZEGLAD ELEKTROTECHNICZNY, 2022, 98 (08): : 52 - 56