The effects of higher temperature setpoints during summer on office workers' cognitive load and thermal comfort

被引:93
|
作者
Zhang, Fan [1 ]
Haddad, Shamila [1 ]
Nakisa, Bahareh [2 ]
Rastgoo, Mohammad Naim [2 ]
Candido, Christhina [1 ]
Tjondronegoro, Dian [2 ]
de Dear, Richard [1 ]
机构
[1] Univ Sydney, Sch Architecture Design & Planning, Sydney, NSW, Australia
[2] Queensland Univ Technol, Sci & Engn Fac, Brisbane, Qld, Australia
关键词
Higher temperature setpoints; Air-conditioning; Cognitive load; Thermal comfort; INDOOR AIR-TEMPERATURE; HUMAN-PERFORMANCE; MENTAL WORKLOAD; PRODUCTIVITY; ENVIRONMENT; BUILDINGS; EVALUATE; QUALITY; DESIGN; HEAT;
D O I
10.1016/j.buildenv.2017.06.048
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Typical commercial lease agreements in Australia stipulate 22.5 +/- 1.5 degrees C in summer as the acceptable thermal condition that buildings have to meet, even though the overcooling incurs excessive and unnecessary energy use, gas emissions and financial expense. An argument that backs up this practice asserts that office workers' productivity and comfort will be jeopardised outside this temperature range. This paper investigated whether the office environments with a practical higher temperature setpoint can still be cognitively efficient and comfortable for office workers. In a controlled climate chamber, 26 office workers experienced the typical summer indoor temperature condition in Australia (22 degrees C) followed by the condition with a higher temperature setpoint (25 degrees C). In both conditions, subjects were required to fulfil Cambridge Brain Science (CBS) cognitive performance tests, NASA Task Load Index (NASA-TLX), and thermal comfort and air quality questionnaires. Meanwhile, participants' electroencephalogram (EEG) and heart rate (HR) were recorded under three different difficulty levels of Paced Auditory Serial Addition Tests (PASAT). Results showed that CBS test scores were not significantly affected by temperature; a higher temperature of 25 degrees C incurred a significantly reduced cognitive load for subjects, as has been observed by NASA-TLX, but probably due to the learning effect; the comparison between EEG and FIR features during different temperatures did not show any significant difference. Participants' thermal comfort was not significantly jeopardized by the 3 degrees C temperature setback either. Results from this study favourably support a practical setback of temperature setpoints in Australian office buildings during summer. (C) 2017 Elsevier Ltd. All rights reserved.
引用
收藏
页码:176 / 188
页数:13
相关论文
共 50 条
  • [1] Effects of climate changes on building energy demand and thermal comfort in Canadian office buildings adopting different temperature setpoints
    Jafarpur, Pouriya
    Berardi, Umberto
    JOURNAL OF BUILDING ENGINEERING, 2021, 42
  • [2] Energy consequences of Comfort-driven temperature setpoints in office buildings
    Aryal, Ashrant
    Becerik-Gerber, Burcin
    ENERGY AND BUILDINGS, 2018, 177 : 33 - 46
  • [3] The degree of adaptive thermal comfort in office workers in a hot-summer Mediterranean climate
    Al-Atrash, Farah
    Hellwig, Runa T.
    Wagner, Andreas
    ENERGY AND BUILDINGS, 2020, 223
  • [4] AIR-CONDITIONING TEMPERATURE ZONES FOR THERMAL COMFORT OF OFFICE AND RESIDENTIAL BUILDINGS IN SUMMER
    Li, Li
    FIFTH INTERNATIONAL WORKSHOP ON ENERGY AND ENVIRONMENT OF RESIDENTIAL BUILDINGS AND THIRD INTERNATIONAL CONFERENCE ON BUILT ENVIRONMENT AND PUBLIC HEALTH, VOL I AND II, PROCEEDINGS, 2009, : 1160 - 1166
  • [5] NUMERICAL EVALUATION OF THERMAL COMFORT IN AN OFFICE ROOM IN SUMMER
    Wang, Hanqing
    Xie, Dong
    Kou, Guangxiao
    Hu, Jianjun
    FIFTH INTERNATIONAL WORKSHOP ON ENERGY AND ENVIRONMENT OF RESIDENTIAL BUILDINGS AND THIRD INTERNATIONAL CONFERENCE ON BUILT ENVIRONMENT AND PUBLIC HEALTH, VOL I AND II, PROCEEDINGS, 2009, : 1095 - 1102
  • [6] Office thermal environment that maximizes workers' thermal comfort and productivity
    Kawakubo, Shun
    Sugiuchi, Masaki
    Arata, Shiro
    BUILDING AND ENVIRONMENT, 2023, 233
  • [7] Human health and thermal comfort of office workers in Singapore
    Chen, Ailu
    Chang, Victor W. -C.
    BUILDING AND ENVIRONMENT, 2012, 58 : 172 - 178
  • [8] THERMAL AND COMFORT SENSATION OF WORKERS OF A PRINTING FACTORY IN SUMMER
    KUNO, Y
    TOCHIHARA, Y
    OHIKE, T
    YOSHIDA, K
    INTERNATIONAL JOURNAL OF BIOMETEOROLOGY, 1978, 22 (04) : 332 - 333
  • [9] Impact of summer office set air-conditioning temperature on energy consumption and thermal comfort
    刘红
    马小磊
    高亚峰
    Journal of Central South University, 2009, 16 (S1) : 6 - 11
  • [10] Impact of summer office set air-conditioning temperature on energy consumption and thermal comfort
    Liu Hong
    Ma Xiao-lei
    Gao Ya-feng
    JOURNAL OF CENTRAL SOUTH UNIVERSITY OF TECHNOLOGY, 2009, 16 : 6 - 11