Study of Improved RSS Algorithm for Ultrasonic Array Applied to PD Location in Transformer

被引:24
|
作者
Luo Yongfen [1 ]
Du Fei [1 ]
Pan Wei [1 ]
Gao Jiaping [1 ]
机构
[1] Xi An Jiao Tong Univ, Sch Elect Engn, Xian 710049, Peoples R China
基金
中国国家自然科学基金;
关键词
Partial discharge (PD); wideband focus; high-order cumulants; virtual array expansion; noise suppression; POWER TRANSFORMERS;
D O I
10.1109/JSEN.2015.2432058
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
An improved rotated sub-space (RSS) algorithm for the application of array technology in partial discharge (PD) location in transformer. The algorithm is based on classic RSS algorithm and high-order cumulants, and it is studied through numerical simulation and experimental tests. Based on an L-shaped and a cross-shaped array, the simulation of single and multiple PD source direction is carried out to compare the classic RSS algorithm with improved RSS algorithm. The results confirm the processing capacity in wideband focus, aperture expansion, enhance of directing, and noise suppression of improved RSS algorithm. Moreover, both algorithms are used for PD location experiments, showing that the error of improved RSS algorithm is similar to 3 degrees. Improved RSS algorithm solves the problem of wideband focusing in PD location, enhances the performance of the array aperture and directing, achieves the effect of the array consists of much more elements with a virtual expansion, simplifying the follow-up circuit.
引用
收藏
页码:4986 / 4991
页数:6
相关论文
共 50 条
  • [1] Modified RSS Algorithm for Ultrasonic Array Applied to PD Direction in Transformer
    Wang G.
    Du F.
    Pan W.
    Wang T.
    Luo Y.
    Zhao X.
    Gaodianya Jishu/High Voltage Engineering, 2019, 45 (08): : 2509 - 2514
  • [2] Research on Ultrasonic Array Location of two PD Sources in Power Transformer
    Xie Qing
    Li Ningyuan
    Huang Huaping
    Li Yanqing
    Lu Fangcheng
    Wang Nan
    2010 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2010,
  • [3] The study of phased-ultrasonic receiving-planar array transducer for PD location in power transformer
    Jisheng, Li
    Yongfen, Luo
    Junhao, Li
    Yanming, Li
    PRZEGLAD ELEKTROTECHNICZNY, 2011, 87 (03): : 324 - 328
  • [4] Study of cross-shaped ultrasonic array sensor applied to partial discharge location in transformer oil
    Li, Jisheng
    Xin, Xiaohu
    Luo, Yongfen
    Ji, Haiying
    Li, Yanming
    Deng, Junbo
    REVIEW OF SCIENTIFIC INSTRUMENTS, 2013, 84 (11):
  • [5] Application of improved genetic algorithm in ultrasonic location of transformer partial discharge
    Zhu, Youchan
    Zhou, Li
    Xu, Haisheng
    NEURAL COMPUTING & APPLICATIONS, 2020, 32 (06): : 1755 - 1764
  • [6] Application of improved genetic algorithm in ultrasonic location of transformer partial discharge
    Youchan Zhu
    Li Zhou
    Haisheng Xu
    Neural Computing and Applications, 2020, 32 : 1755 - 1764
  • [7] Relocatable Ultrasonic Array and UHF Combined Sensor Applied to PD Location in Oil
    Xin Xiaohu
    Luo Yongfen
    Tang Xiao
    Chen Peng
    Li Yanming
    IEEE SENSORS JOURNAL, 2014, 14 (02) : 357 - 361
  • [8] Application of Genetic Algorithm in PD Source Location in Transformer Oil
    Du Ron-ping
    Jiang Li-ming
    Liu Sheng-qi
    Li Wei-bin
    Bian Xiao-liang
    Chen Lu
    Si Wen-rong
    2020 5TH INTERNATIONAL CONFERENCE ON SMART GRID AND ELECTRICAL AUTOMATION (ICSGEA 2020), 2020, : 567 - 571
  • [9] Study of cross-shaped ultrasonic array senor applied to partial discharge location in transformers
    Xin, X. (xxh8086@stu.xjtu.edu.cn), 1600, Chinese Society for Electrical Engineering (33):
  • [10] Comparison of DOA Algorithms Applied to Ultrasonic Arrays for PD Location in Oil
    Luo Yongfen
    Xin Xiaohu
    Du Fei
    Tang Xiao
    Li Yanming
    IEEE SENSORS JOURNAL, 2015, 15 (04) : 2316 - 2323