A Systematic Approach to Light Load Calculation for DG Un-Intentional Islanding

被引:1
|
作者
Chen, Le [1 ]
Saylor, Joseph [2 ]
Clark, Aaron [2 ]
Zhao, Jiecheng [2 ]
Velez, Francisco [2 ]
Liu, Hesen [2 ]
Liu, Yilu [1 ,3 ]
机构
[1] Univ Tennessee, Knoxville, TN 37996 USA
[2] Dominion Energy, Richmond, VA 23220 USA
[3] Oak Ridge Natl Lab, Oak Ridge, TN 37830 USA
关键词
DG; protection; anti-islanding; un-intentional islanding; IEEE; 1547; light load; EMS;
D O I
10.1109/td39804.2020.9299886
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
With the influx of distributed generation (DG) penetration, power utilities have adopted active anti-islanding protection methods to prevent an unintentional islanding condition. One commonly used protection scheme is implemented through the use of a transfer trip from the upline connected substation to the DG facility and is required when the capacity of connected DGs exceed a certain threshold of local minimum load. The threshold established by standard IEEE 1547.2-2009 states that a 3:1 minimum load to generation ratio is acceptable to ensure the DG will not sustain an unintentional island. However, the term "minimum load" is not precisely defined in any standard, and in practice, a light load value is chosen by engineers through manual methods that can be inconsistent, not representative and change drastically based on various cases. To solve this problem, this paper proposes a new light load calculation method creating consistency and better accuracy; the method has been implemented in .NET C# application and is used within Dominion Energy.
引用
收藏
页数:5
相关论文
共 3 条
  • [1] Distributed Energy Resource Overvoltage during Un-intentional Islanding
    Chen, Le
    Zhao, Jiecheng
    Liu, Ren
    Velez-Cedeno, Francisco
    Liu, Hesen
    Liu, Yilu
    2019 IEEE INDUSTRY APPLICATIONS SOCIETY ANNUAL MEETING, 2019,
  • [2] Monte Carlo Simulation by Using a Systematic Approach to Assess Distribution System Reliability Considering Intentional Islanding
    Conti, Stefania
    Rizzo, Santi Agatino
    IEEE TRANSACTIONS ON POWER DELIVERY, 2015, 30 (01) : 64 - 73
  • [3] End-to-End Deep Graph Convolutional Neural Network Approach for Intentional Islanding in Power Systems Considering Load-Generation Balance
    Sun, Zhonglin
    Spyridis, Yannis
    Lagkas, Thomas
    Sesis, Achilleas
    Efstathopoulos, Georgios
    Sarigiannidis, Panagiotis
    SENSORS, 2021, 21 (05) : 1 - 15