Switching Surge Analysis of an EHV Air-Insulated Substation Using the 3-D FDTD Method

被引:13
|
作者
Tatematsu, Akiyoshi [1 ]
Moriguchi, Soichi [2 ]
Ueda, Toshiaki [3 ]
机构
[1] Cent Res Inst Elect Power Ind, Yokosuka, Kanagawa 2400196, Japan
[2] Chubu Elect Power Co Inc, Nagoya, Aichi 4598522, Japan
[3] Daido Univ, Dept Elect & Elect Engn, Nagoya, Aichi 4578530, Japan
关键词
Air-insulated substation; electrical safety; finite-difference time-domain (FDTD); grounding; switching transients; TRANSIENT ELECTROMAGNETIC-FIELDS; THIN WIRES; SIMULATION; TRANSMISSION; INTERFERENCE; PREDICTION; BOUNDARY; CIRCUITS; SYSTEMS; SOIL;
D O I
10.1109/TPWRD.2018.2807878
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Switching overvoltages on busbars occur during the operation of circuit breakers and disconnectors in power plants and substations. The transient electromagnetic interferences arising from the switching surges may cause disturbances in sensitive electronic devices in low-voltage control circuits and may induce voltages on other busbars grounded for maintenance. To suppress the effect of electromagnetic interferences properly, it is useful to predict surge phenomena and design effective protection methodologies. The finite-difference time-domain (FDTD) method, which is a full-wave numerical approach, has become an effective tool for analyzing surge phenomena in a 3-D arrangement. In this study, first, we propose techniques for applying the FDTD method to the switching surge analysis of an extremely high voltage air-insulated substation. Second, using the proposed techniques, we calculate voltages induced on a grounded busbar due to a restrike at a disconnector during its operation in a 500 kV air-insulated substation and compare the calculated results with measured results for validation.
引用
收藏
页码:2324 / 2334
页数:11
相关论文
共 50 条
  • [1] FDTD-Based Lightning Surge Simulation of an HV Air-Insulated Substation With Back-Flashover
    Tatematsu, Akiyoshi
    Ueda, Toshiaki
    IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, 2016, 58 (05) : 1549 - 1560
  • [2] Overvoltages in Secondary Circuits of Air-Insulated Substation Due to Disconnector Switching
    Bajramovic, Zijad
    Turkovic, Irfan
    Mujezinovic, Adnan
    Carsimamovic, Adnan
    Muharemovic, Aida
    2012 IEEE INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY (POWERCON), 2012,
  • [3] Analysis of electromagnetic transients in secondary circuits due to disconnector switching in 400 kV air-insulated substation
    Filipovic-Grcic, B.
    Uglesic, I.
    Milardic, V.
    Filipovic-Grcic, D.
    ELECTRIC POWER SYSTEMS RESEARCH, 2014, 115 : 11 - 17
  • [4] Localization Method for Multiple Partial Discharge Sources in Air-insulated Substation by Using Plane Intersection Method
    Zhu M.
    Liu Q.
    Wang Y.
    Deng J.
    Zhang G.
    Guo A.
    Zhang, Guanjun (gjzhang@mail.xjtu.edu.cn), 2018, Science Press (44): : 2970 - 2976
  • [5] 3D Localization Method of Partial Discharge in Air-Insulated Substation Based on Improved Particle Swarm Optimization Algorithm
    Li, Pengfei
    Peng, Xinjie
    Yin, Kaiyang
    Xue, Yaxu
    Wang, Rongqing
    Ma, Zhengsen
    SYMMETRY-BASEL, 2022, 14 (06):
  • [6] Statistical analysis on measured lightning overvoltage surges in a 110 kV air-insulated substation
    Sima, Wenxia
    Lan, Xing
    Yang, Qing
    Yuan, Tao
    IET SCIENCE MEASUREMENT & TECHNOLOGY, 2015, 9 (01) : 28 - 36
  • [7] Grading Structure Design of Surge Arrester for 1000-kV Ultra-high Voltage Air-insulated Substation
    He, Jinliang
    Hu, Jun
    Zhang, Bo
    ICHVE 2008: 2008 INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION, 2008, : 84 - 87
  • [8] Analysis of transient EMI of air-insulated substation disconnect operation based on Wigner-Ville Distribution
    Tao, JS
    Chen, SX
    Zhang, XX
    EMC 2005: IEEE International Symposium on Electromagnetic Compatibility, Vols 1-3, Proceedings, 2005, : 851 - 855
  • [9] Localization of Multiple Partial Discharge Sources in Air-Insulated Substation Using Probability-Based Algorithm
    Zhu, Ming-Xiao
    Wang, Yan-Bo
    Liu, Qing
    Zhang, Jia-Ning
    Deng, Jun-Bo
    Zhang, Guan-Jun
    Shao, Xian-Jun
    He, Wen-Lin
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2017, 24 (01) : 157 - 166
  • [10] Localization of E-M Interference Sources in Air-Insulated Substation using VHF/UHF Antenna Arrays
    Roehrich, Jozef
    Zydron, Pawel
    Szafraniak, Bartlomiej
    PROCEEDINGS OF THE 9TH INTERNATIONAL SCIENTIFIC SYMPOSIUM ON ELECTRICAL POWER ENGINEERING (ELEKTROENERGETIKA 2017), 2017, : 301 - 305