On criteria of optimized application of AMF- and RMF-contact systems in vacuum interrupters

被引:0
|
作者
Renz, R [1 ]
机构
[1] Siemens AG, Berlin, Germany
来源
ISDEIV: XIXTH INTERNATIONAL SYMPOSIUM ON DISCHARGES AND ELECTRICAL INSULATION IN VACUUM, VOLS 1 AND 2, PROCEEDINGS | 2000年 / 19卷
关键词
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In case of interrupting high ac-currents in vacuum, a metal vapour are burns between the separating contacts, till the next current-zero. However, if the current exceeds the range of approximately 10 kA the are will pinch due to its own magnetic field. In order to avoid a local contact overheating there are two possibilities: Movement of the constricted are on the contact surface by a radial magnetic field (RMF) Prevention of are constriction by an axial magnetic field (AMF) In a short overview the functional principles and physics of RMF and AMF are given. Pros and cons of RMF versus AMF with regard to interrupting capability, electrical resistance, tubes dimension and production costs will be compared for the low, medium and high voltage range.
引用
收藏
页码:176 / 179
页数:4
相关论文
共 10 条
  • [1] New developments of vacuum interrupters based on RMF and AMF technologies
    Fink, H
    Gentsch, D
    Heimbach, M
    Pilsinger, G
    Shang, WK
    ISDEIV: XVIIITH INTERNATIONAL SYMPOSIUM ON DISCHARGES AND ELECTRICAL INSULATION IN VACUUM - PROCEEDINGS, VOLS 1 AND 2, 1998, 18 : 463 - 466
  • [2] Arc control systems for AMF high voltage vacuum interrupters - modeling the contact gap
    Falkingham, L. T.
    Molan, W.
    PROCEEDINGS OF THE 2014 26TH INTERNATIONAL SYMPOSIUM ON DISCHARGES AND ELECTRICAL INSULATION IN VACUUM (ISDEIV-2014), 2014, : 125 - 128
  • [3] Criteria for the Application of Vacuum Interrupters in HVDC Circuit Breakers
    Slade, Paul G.
    2022 IEEE 67TH HOLM CONFERENCE ON ELECTRICAL CONTACTS (HLM), 2022, : 80 - 86
  • [4] Prestrike inrush current arc behavior in AMF vacuum interrupters subjected to contact plate slots
    Yu, Yongxiang
    Yao, Daojin
    Shi, Jie
    Zhou, Wei
    ELECTRIC POWER SYSTEMS RESEARCH, 2021, 201
  • [5] Electrode processes in AMF-contact systems of medium voltage vacuum interrupters when switching the limiting current. A Review
    Shkol'nik, S. M.
    29TH INTERNATIONAL SYMPOSIUM ON DISCHARGES AND ELECTRICAL INSULATION IN VACUUM (ISDEIV 2020), 2021, : 188 - 193
  • [6] Experimental investigation and numerical simulation of triggered vacuum arc behavior under TMF/RMF-AMF contact
    Wang, Lijun
    Deng, Jie
    Qin, Kang
    Zhang, Xiao
    Jia, Shenli
    JOURNAL OF PHYSICS D-APPLIED PHYSICS, 2016, 49 (23)
  • [7] Processes on Contacts and Thermal State of Contact Surfaces in AMF-Contact Systems of Medium-Voltage Vacuum Interrupters When Switching the Limiting Current: A Review
    Shkolnik, Sergey M.
    IEEE TRANSACTIONS ON PLASMA SCIENCE, 2022, 50 (09) : 2634 - 2641
  • [8] Influence of Contact Plate Parameters and Eddy Currents on Residual Flux Decay in AMF-Type Vacuum Interrupters
    Bhat, Rahul
    Kulkarni, S. V.
    IEEE TRANSACTIONS ON POWER DELIVERY, 2018, 33 (06) : 2812 - 2821
  • [9] 3-D magnetic field simulation of a new-type contact with TMF-AMF for vacuum interrupters
    Dong, Huajun
    Yang, Haijun
    Guo, Yingjie
    Xiang, Chuan
    Kang, Kai
    Guo, Fangzhun
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2015, 30 (05): : 111 - 118
  • [10] Effects of Optimized Switching Contact Materials, Aging, and Superimposed Axial Magnetic Field on Chopping Current in Vacuum Interrupters
    Fischer, Markus
    Beltle, Michael
    Tenbohlen, Stefan
    Gentsch, Dietmar
    Ebbinghaus, Werner
    IEEE TRANSACTIONS ON PLASMA SCIENCE, 2024, 52 (09) : 4419 - 4427