On-line Analysis of Power Transformer Bushings

被引:6
|
作者
Faifer, M. [1 ]
Ottoboni, R. [1 ]
Cristaldi, L. [1 ]
Toscani, S. [1 ]
机构
[1] Politecn Milan, Dipartimento Elettrotecn, I-20133 Milan, Italy
关键词
diagnostic; power transformer bushings; power factor and capacitance;
D O I
10.1109/IMTC.2011.5944188
中图分类号
TH7 [仪器、仪表];
学科分类号
0804 ; 080401 ; 081102 ;
摘要
The approach to the maintenance of devices and systems has strongly changed in the last years, thanks to the availability of more and more sophisticated technologies. In particular, when the servicing involves very critical processes, a new interesting strategy is represented by the Condition Based Maintenance (CBM). It is based on the continuous observation of some physical parameters which permits to infer the status of the system and thus to detect the need to service it. In this paper a novel monitoring method is proposed. It allows the application of CBM techniques to one of the least reliable components in HV and MV systems: the transformer bushing. Starting from some theoretical and practical considerations, it will be shown that it is possible to measure the capacitance and the power factor of transformer bushing, without putting the plant out of order. It is known that these two parameters are particularly useful to schedule the maintenance activity. This goal can be achieved by superimposing a high frequency sinusoidal voltage between the bushing tap and the ground. Some considerations prove that having chosen a proper frequency, the consequent current is much more sensitive to the bushing capacitance than to the other impedances. Finally the architecture of a measurement system is also presented.
引用
收藏
页码:1103 / 1108
页数:6
相关论文
共 50 条
  • [1] On-line monitoring and diagnoses of power transformer bushings
    Setayeshmehr, Alireza
    Akbari, Alireza
    Borsi, Hossein
    Gockenbach, Ernst
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2006, 13 (03) : 608 - 615
  • [2] Advantages vs. risks with on-line monitoring of transformer bushings
    Jonsson, Lars
    2021 IEEE ELECTRICAL INSULATION CONFERENCE (EIC), 2021, : 556 - 559
  • [3] On-line Monitoring of Transformer Bushings using a new Decentralized Measurement System
    Riendeau, S.
    Picher, P.
    Leonard, F.
    Gauvin, M.
    Bertrand, H.
    CONFERENCE RECORD OF THE 2010 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION (ISEI), 2010,
  • [4] On-line monitoring of transformer bushings by advanced measuring method at neutral point
    Zhou, Haiyang
    Li, Hui
    Yan, Zhang
    Gaodianya Jishu/High Voltage Engineering, 2002, 28 (05):
  • [5] A Novel Warning Strategy of Transformer Bushings Based on Mathematical Statistics Analysis of Historical On-line Monitoring Data
    Li, Feng
    Sun, Xudong
    Wang, Hongbin
    Liang, Wenjin
    Ding, Weidong
    2ND INTERNATIONAL CONFERENCE ON SENSORS, INSTRUMENT AND INFORMATION TECHNOLOGY (ICSIIT 2015), 2015, : 40 - 45
  • [6] On-line three-phase differential partial discharge localization in transformer bushings
    Meyer, Hans Kristian Hygen
    Eberg, Espen
    Lundgaard, Lars
    2021 IEEE ELECTRICAL INSULATION CONFERENCE (EIC), 2021, : 80 - 83
  • [7] An Intelligent On-Line Inspection and Warning System Based on Infrared Image for Transformer Bushings
    Zhao, Zhenbing
    Xu, Guozhi
    Qi, Yincheng
    Pan, Defeng
    RECENT ADVANCES IN ELECTRICAL & ELECTRONIC ENGINEERING, 2016, 9 (01) : 53 - 62
  • [8] On-line transformer gas analysis
    Pyke, S
    PROCEEDINGS OF THE AMERICAN POWER CONFERENCE, VOL 58, PTS I AND II, 1996, 58 : 289 - 292
  • [9] On-line Monitoring Method for Transformer Bushings with Moisture Based on Air Humidity Perception in Conservator
    Jia L.
    Wang T.
    Xiao W.
    Shu S.
    Li W.
    Zheng Y.
    Gaodianya Jishu/High Voltage Engineering, 2020, 46 (09): : 3114 - 3123
  • [10] A New Method for On-Line Monitoring of Bushings and Partial Discharges of Power Transformers
    Koch, Maik
    Krueger, Michael
    PROCEEDINGS OF 2012 IEEE INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS (IEEE CMD 2012), 2012, : 1205 - 1208