Testing Sensitivity of A-Type Residual Current Devices to Earth Fault Currents with Harmonics

被引:11
|
作者
Czapp, Stanislaw [1 ]
机构
[1] Gdansk Univ Technol, Fac Elect & Control Engn, PL-80233 Gdansk, Poland
关键词
current sensor; earth fault; harmonics; low-voltage systems; residual current devices;
D O I
10.3390/s20072044
中图分类号
O65 [分析化学];
学科分类号
070302 ; 081704 ;
摘要
In many applications, modern current-using equipment utilizes power electronic converters to control the consumed power and to adjust the motor speed. Such equipment is used both in industrial and domestic installations. A characteristic feature of the converters is producing distorted earth fault currents, which contain a wide spectrum of harmonics, including high-order harmonics. Nowadays, protection against electric shock in low-voltage power systems is commonly performed with the use of residual current devices (RCDs). In the presence of harmonics, the RCDs may have a tripping current significantly different from that provided for the nominal sinusoidal waveform. Thus, in some cases, protection against electric shock may not be effective. The aim of this paper is to present the result of a wide-range laboratory test of the sensitivity of A-type RCDs in the presence of harmonics. This test has shown that the behavior of RCDs in the presence of harmonics can be varied, including the cases in which the RCD does not react to the distorted earth fault current, as well as cases in which the sensitivity of the RCD is increased. The properties of the main elements of RCDs, including the current sensor, for high-frequency current components are discussed as well.
引用
收藏
页数:20
相关论文
共 42 条
  • [1] The Effect of Earth Fault Current Harmonics on Tripping of Residual Current Devices
    Czapp, Stanislaw
    2008 INTERNATIONAL SCHOOL ON NONSINUSOIDAL CURRENTS AND COMPENSATION, 2008, : 66 - 71
  • [2] The effect of earth fault current harmonics on tripping of residual current devices
    Czapp, Stanislaw
    PRZEGLAD ELEKTROTECHNICZNY, 2009, 85 (01): : 196 - 201
  • [3] Behavior of Residual Current Devices at Earth Fault Currents with DC Component
    Czapp, Stanislaw
    Tariq, Hanan
    Cieslik, Slawomir
    SENSORS, 2022, 22 (21)
  • [5] New Method for Calculation of the Harmonics in the Residual Earth Fault Current in Isolated and Compensated Networks
    Schmidt, Uwe
    Frowein, Karla
    Druml, Gemot
    Sehegner, Peter
    10TH INTERNATIONAL CONFERENCE 2016 ELECTRIC POWER QUALITY AND SUPPLY RELIABILITY CONFERENCE (PQ), 2016, : 309 - 313
  • [6] Measurement of earth fault loop impedance in circuits with time-delay type residual current devices
    Borowski, Kornel
    Czapp, Stanislaw
    PRZEGLAD ELEKTROTECHNICZNY, 2023, 99 (02): : 289 - 292
  • [8] Residual current devices tripping current in case of earth fault in the motor circuit supplied via frequency converter
    Czapp, Stanislaw
    Wlas, Miroslaw
    PRZEGLAD ELEKTROTECHNICZNY, 2010, 86 (04): : 296 - 301
  • [9] A novel method to reduce the harmonic currents in the residual earth fault current during a single phase to ground fault in compensated grids
    Steglich, Michael
    Loewe, Christopher
    Bauernschmitt, Bjoern
    Rehtanz, Christian
    Boehm, Ralf
    Franke, Joerg
    PROCEEDINGS OF 2019 IEEE PES INNOVATIVE SMART GRID TECHNOLOGIES EUROPE (ISGT-EUROPE), 2019,
  • [10] The Impact of Higher-Order Harmonics on Tripping of Residual Current Devices
    Czapp, Stanislaw
    2008 13TH INTERNATIONAL POWER ELECTRONICS AND MOTION CONTROL CONFERENCE, VOLS 1-5, 2008, : 2059 - +