Charge behavior in flowing oil in oil/pressboard insulation system by electro-optic field measurement

被引:16
|
作者
Okubo, H [1 ]
Wakamatsu, M
Inoue, N
Kato, K
Koide, H
机构
[1] Nagoya Univ, Dept Elect Engn, Chikusa Ku, Nagoya, Aichi 4648603, Japan
[2] Japan AE Power Syst Corp, Ichihara 2900067, Japan
关键词
charge behavior; flowing charged oil; oil/pressboard transformer model; Kerr effect; electric field measurement;
D O I
10.1109/TDEI.2003.1255772
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The electrical insulation structure of most power transformers is a combination of insulating oil and solid materials. One of the crucial problems we face in transformer operation is flow electrification, which occurs at a flowing oil/solid material interface. Thus, for the transformer insulation design, we need to clarify the flow electrification phenomena. In this paper, we measured the electric field strength in an oil/pressboard composite insulation system using an electro-optic method of the Kerr effect. We obtained the time variation of electric field distribution in both flowing uncharged and charged oil. It is notable that we could quantitatively clarify the electric field distortion in flowing charged oil by flow electrification. Furthermore, we measured the leakage current from divided electrodes and derived a charge density distribution along the flow direction. Finally, we quantitatively discussed the electric field distribution and the charge behavior from the measurement results.
引用
收藏
页码:956 / 962
页数:7
相关论文
共 50 条
  • [1] Charge Behavior in flowing oil at oil/pressboard interface by electro-optic field measurement
    Okubo, H
    Inoue, N
    Wakamatsu, M
    Kato, K
    Shimizu, R
    Nakagami, Y
    PROCEEDINGS OF THE 2002 IEEE 14TH INTERNATIONAL CONFERENCE ON DIELECTRIC LIQUIDS, 2002, : 178 - 181
  • [2] Investigation of charge behavior in flowing transformer oil/pressboard composite insulation system by electro-optic field measurement
    Okubo, H
    Hashiba, Y
    Kato, K
    Shimizu, R
    Nakagami, Y
    Miyamoto, M
    IAS 2000 - CONFERENCE RECORD OF THE 2000 IEEE INDUSTRY APPLICATIONS CONFERENCE, VOLS 1-5, 2000, : 732 - 738
  • [3] Study on charge behavior in flowing transformer oil/pressboard composite insulation system using electro-optic field measurement
    Kato, K.
    Hashiba, V.
    Nakagami, Y.
    Miyamoto, M.
    Okubo, H.
    IEEE International Conference on Conduction and Breakdown in Dielectric Liquids, ICDL, 1999, : 349 - 352
  • [4] DC field measurement in oil/pressboard composite insulation system by electro-optic Kerr effect
    Kato, K
    Wakamatsu, M
    Inoue, N
    Shimizu, R
    Nakagami, Y
    Okubo, H
    PROCEEDINGS OF THE 2002 IEEE 14TH INTERNATIONAL CONFERENCE ON DIELECTRIC LIQUIDS, 2002, : 293 - 296
  • [5] Charge behavior in flowing charged oil/pressboard composite insulation system based on electric field measurement
    Wakamatsu, M
    Kato, K
    Koide, H
    Okubo, H
    2003 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, 2003, : 189 - 192
  • [6] HVDC Electrical Insulation Performance in Oil/Pressboard Composite Insulation System Based on Kerr Electro-Optic Field Measurement and Electric Field Analysis
    Okubo, Hitoshi
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2018, 25 (05) : 1785 - 1797
  • [7] Kerr electro-optic measurement of electric field distribution in rapeseed ester oil and pressboard composite system
    Nakamura, K
    Kato, K
    Koide, H
    Fujii, K
    Okubo, H
    ICDL: 2005 IEEE INTERNATIONAL CONFERENCE ON DIELECTRIC LIQUIDS, 2005, : 405 - 408
  • [8] DC field measurement in oil/plressboard composite insulation system by electro-optic Kerr effect
    Wakamatsu, M
    Kato, K
    Inoue, N
    Koide, H
    Okubo, H
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2003, 10 (06) : 942 - 947
  • [9] Kerr electro-optic field measurement in transformer oil solid dielectrics composite insulation system
    Okubo, H
    Shimizu, R
    Kato, K
    Hayakawa, N
    Hikita, M
    ICDL 1996 - 12TH INTERNATIONAL CONFERENCE ON CONDUCTION AND BREAKDOWN IN DIELECTRIC LIQUIDS, 1996, : 389 - 392
  • [10] Kerr electro-optic field measurement and charge dynamics in transformer-oil/solid composite insulation systems
    Okubo, H
    Shimizu, R
    Sawada, A
    Kato, K
    Hayakawa, N
    Hikita, M
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 1997, 4 (01) : 64 - 70