A case study of rupture in overhead ground wire twined by armor rod

被引:5
|
作者
Deng, Honglei [1 ]
Peng, Ruidong [1 ]
Zhong, Meishan [1 ]
Yang, Rui [2 ]
Liang, Yongchun [3 ]
Guo, Deming [1 ]
Liu, Gang [1 ]
机构
[1] South China Univ Technol, Sch Elect Power Engn, Guangzhou 510640, Guangdong, Peoples R China
[2] Dongguan Power Supply Bur Guangdong Power Grid Co, Dongguan 523008, Guangdong, Peoples R China
[3] Elect Power Res Inst Guangdong Power Grid Co Ltd, Guangzhou 510080, Guangdong, Peoples R China
基金
中国国家自然科学基金;
关键词
Overhead ground wire; Armor rod; Rupture; Discharge; Skin effect; MECHANICAL-PROPERTIES; CABLES; DAMAGE;
D O I
10.1016/j.engfailanal.2021.105844
中图分类号
TH [机械、仪表工业];
学科分类号
0802 ;
摘要
The armor rod (AR) is used to repair the damaged overhead ground wire (OGW) and prevent the wear of the OGW in the suspension clamp in engineering. Once the OGW at the AR terminal breaks, it may lead to temporary blackout, which also causes the severe economic losses, or even threatening public safety. However, there are few literature or report about this type of accident at present. Therefore, based on a rupture accident of OGW at the AR terminal, the reason for this accident was investigated in this paper. Firstly, the description of the accident background and the material analysis for the accident sample were presented to preliminarily determine the damage characteristics of OGW and the cause of the accident. Secondly, simulation experiments for the transient temperature rise of the AR terminal were conducted. The macroscopic morphology characteristics of the experimental samples were also analyzed. Finally, based on the electromagnetic thermal coupling, a finite element model of the AR terminal of OGW was established. The overheating mechanism at the AR terminal was also discussed according to the model. The discharge occurrs at the AR terminal under the short-circuit current (SCC), and it is also the prime factor that causes the high temperature of OGW. The research methods and conclusions in this paper can provide theoretical guidance for the analysis of similar accidents and the optimization design of structures.
引用
收藏
页数:15
相关论文
共 50 条
  • [1] A case study of rupture in overhead ground wire twined by armor rod
    Deng, Honglei
    Peng, Ruidong
    Zhong, Meishan
    Yang, Rui
    Liang, Yongchun
    Guo, Deming
    Liu, Gang
    Engineering Failure Analysis, 2022, 131
  • [2] Development of a preformed armor rod repair robot for optical fiber composite overhead ground wire (OPGW)
    Wang, Yuehua
    Liu, Yanheng
    Kim, Taegyun
    MECHATRONICS, 2025, 106
  • [3] Axial Thermal Circuit Model-Based Calculation of Contact Resistance of Contact Surface Between the Overhead Ground Wire and Armor Rod
    Liu G.
    Guo D.
    Zheng W.
    Huang J.
    Li J.
    Yang Y.
    Chen X.
    Pan C.
    Huanan Ligong Daxue Xuebao/Journal of South China University of Technology (Natural Science), 2020, 48 (07): : 9 - 19
  • [4] Calculation of Equivalent Resistance for Ground Wires Twined with Armor Rods in Contact Terminals
    Liu, Gang
    Guo, Deming
    Wang, Pengyu
    Deng, Honglei
    Hong, Xiaobin
    Tang, Wenhu
    ENERGIES, 2018, 11 (04)
  • [5] The Study of DC Melting Ice for Overhead Ground Wire
    Sun, Peng
    Chen, Shaohui
    Zhang, Shaoquan
    2011 INTERNATIONAL CONFERENCE ON ELECTRONICS, COMMUNICATIONS AND CONTROL (ICECC), 2011, : 2960 - 2963
  • [6] Improvement Measures of Armor Rods Segment of Overhead Ground Wire Based on Multi-field Coupling
    Liu G.
    Guo D.
    Zheng W.
    Li J.
    Chen X.
    Chen X.
    Gaodianya Jishu/High Voltage Engineering, 2021, 47 (07): : 2489 - 2497
  • [7] Electrothermal damage numerical analysis for overhead ground wire at terminal of armor rods under short-circuit current
    Li, Hongfa
    Cheng, Lang
    Huang, Beisi
    Cheng, Shaobing
    Lin, Jiayao
    Nie, Wenxiang
    Guo, Deming
    Liu, Gang
    ELECTRICAL ENGINEERING, 2024, : 4313 - 4323
  • [8] A case study of ruptures in overhead ground wire under a large lightning over 400kA
    Liu, Gang
    Peng, Xiangyang
    Zhong, Meishan
    Wang, Rui
    Wang, Pengyu
    Guo, Deming
    Qi, Qi
    ENGINEERING FAILURE ANALYSIS, 2019, 104 : 1211 - 1233
  • [9] Refurbishing existing Overhead Earth Wire with Optical Ground Wire
    Nassereddine, M.
    Rizk, J.
    Hellany, A.
    Nagrial, M.
    2014 49TH INTERNATIONAL UNIVERSITIES POWER ENGINEERING CONFERENCE (UPEC), 2014,
  • [10] Detection for overhead ground wire by lines clustering
    Cheng, Li
    Yao, Wei
    SIGNAL IMAGE AND VIDEO PROCESSING, 2022, 16 (02) : 447 - 455