Mathematical Modeling of Critical Parameters on the Polluted Ceramic Insulators Under AC Voltage: Based on Experimental Tests

被引:6
|
作者
Palangar, Mousalreza Faramarzi [1 ]
Mirzaie, Mohammad [1 ]
机构
[1] Babol Univ Technol, Fac Elect & Comp Engn, Babol Sar, Iran
关键词
Critical parameters; Polluted insulators; Profile factor (M); Mathematical model; FLASHOVER VOLTAGE; BEHAVIOR;
D O I
10.1007/s13369-016-2098-2
中图分类号
O [数理科学和化学]; P [天文学、地球科学]; Q [生物科学]; N [自然科学总论];
学科分类号
07 ; 0710 ; 09 ;
摘要
In this paper, a mathematical model of critical parameters on the polluted ceramic insulators based on experimental analysis has been presented. In these cases, the effect of pollution and humidity on the leakage current and applied voltage of the insulators has been investigated. Also, the effect of the insulator shed on the critical parameters has been considered as the factor M. The profile factor M is the ratio of top level leakage distance to bottom leakage distance of insulator. Indeed, the value of the factor M has been defined as a criterion in experimental tests to determine the insulators' electric strength. As well, to determine the constants of electric arc, the theoretical and experimental results have been compared, thus values of these constants have been determined. So, by presented mathematical model the critical parameters will be predicted. The closeness of results between proposed mathematical model and experiment confirms the veracity of the presented model.
引用
收藏
页码:3501 / 3510
页数:10
相关论文
共 24 条
  • [1] Mathematical Modeling of Critical Parameters on the Polluted Ceramic Insulators Under AC Voltage: Based on Experimental Tests
    Mousalreza Faramarzi Palangar
    Mohammad Mirzaie
    Arabian Journal for Science and Engineering, 2016, 41 : 3501 - 3510
  • [2] Flashover dynamic model of polluted insulators under ac voltage
    Dhahbi-Megriche, N
    Beroual, A
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2000, 7 (02) : 283 - 289
  • [3] Modeling of altitude effects on AC flashover of polluted high voltage insulators
    Rizk, FAM
    Rezazada, AQ
    IEEE TRANSACTIONS ON POWER DELIVERY, 1997, 12 (02) : 810 - 822
  • [4] Predictive dynamic model of the leakage current and flashover voltage of discontinuously polluted insulators under ac voltage: experimental validation
    Dhahbi-Megriche, N.
    Beroual, A.
    JOURNAL OF PHYSICS D-APPLIED PHYSICS, 2007, 40 (24) : 7782 - 7786
  • [5] Dynamic model to predict AC critical flashover voltage of nonuniformly polluted insulators under thermal ionization conditions
    Shahabi, Saeed
    Gholami, Ahmad
    TURKISH JOURNAL OF ELECTRICAL ENGINEERING AND COMPUTER SCIENCES, 2017, 25 (03) : 2322 - 2335
  • [6] Modelling Surface Electric Discharge Propagation on Polluted Insulators under AC Voltage
    Amrani, Mohamed Lamine
    Bouazabia, Slimane
    Fofana, Issouf
    Meghnefi, Fethi
    Jabbari, Marouane
    Khelil, Djazia
    Boudiaf, Amina
    ENERGIES, 2021, 14 (20)
  • [7] Electrical Circuit Flashover Model of Polluted Insulators under AC Voltage Based on the Arc Root Voltage Gradient Criterion
    Yang, Qing
    Wang, Rui
    Sima, Wenxia
    Jiang, Chilong
    Lan, Xing
    Zahn, Markus
    ENERGIES, 2012, 5 (03): : 752 - 769
  • [8] IMPROVEMENT OF THE DYNAMIC MODEL OF POLLUTED INSULATORS UNDER AC VOLTAGE BASED ON THE ELECTRO-THERMAL CHARACTERISTICS
    Wang, Sihua
    Xu, Wanli
    Tian, Mingxing
    UNIVERSITY POLITEHNICA OF BUCHAREST SCIENTIFIC BULLETIN SERIES C-ELECTRICAL ENGINEERING AND COMPUTER SCIENCE, 2018, 80 (04): : 161 - 172
  • [9] AC Flashover Voltage Model for Polluted Suspension Insulators and an Experimental Investigation in Salt Fog
    Dong, Bingbing
    Zhang, Zhu
    Xiang, Nianwen
    Yang, Hejun
    Xu, Shuiqing
    Cheng, Tingli
    IEEE ACCESS, 2020, 8 : 187411 - 187418
  • [10] Experimental study of pollution and simulation on insulators using comsol® under AC voltage
    Benguesmia H.
    Bakri B.
    Khadar S.
    Hamrit F.
    M'ziou N.
    Diagnostyka, 2019, 20 (03): : 21 - 29