SAFE OPERATING LIMITS Generator capability study for offshore oil platforms

被引:4
|
作者
Sutherland, Peter E. [1 ]
机构
[1] GE Energy Serv, Schenectady, NY USA
关键词
MILL;
D O I
10.1109/MIAS.2010.939648
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
In this article, the offshore production platforms two 25-MW turbine generator units were evaluated to determine the safe operating limits of the units if the entire load is to be carried by one generator. A case study is performed to determine whether load shedding will be necessary if only one generator is in operation. The generator reactive capability curve was constructed based on limited data due to the age of the generators. The real power output capability of the turbine-generator combination was evaluated based upon the data provided. The generator was rated in accordance with British Standard BS.2613/1957. The analysis was based upon the requirements the superseding standards, International Electrotechnical Commission (IEC) 60034-1 (2004) and IEC 60034-3 (2005). © 2011 IEEE.