Indoor/Outdoor Relationships of Airborne Particles under Controlled Pressure Difference across the Building Envelope in Korean Multifamily Apartments

被引:10
|
作者
Choi, Dong Hee [1 ]
Kang, Dong Hwa [2 ]
机构
[1] Kyungil Univ, Dept Architectural Engn, Coll Engn, Kyungsan 38428, South Korea
[2] Univ Seoul, Dept Architectural Engn, Coll Urban Sci, Seoul 02504, South Korea
来源
SUSTAINABILITY | 2018年 / 10卷 / 11期
基金
新加坡国家研究基金会;
关键词
particle infiltration; I/O ratio; urban apartments; air leakage; I-O pressure difference; blower door test; AIR-POLLUTION; FINE PARTICLES; PENETRATION; INDOOR; SIZE; DEPOSITION; ULTRAFINE;
D O I
10.3390/su10114074
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
This study investigates indoor/outdoor relationships of airborne particles under controlled pressure difference across the building envelope in Korean multifamily apartments. On-site field experiments on 14 apartment housing units located in urban areas in Korea are conducted to measure the indoor/outdoor ratios of number concentrations of size-resolved particles (0.3-0.5, 0.5-1.0, 1.0-3.0, 3.0-5.0, 5.0-10.0, >10.0 mu m). To set identical pressure difference conditions across the envelope of each housing unit for better comparison of I/O ratio results, and to examine the effect of pressure difference on the I/O relations, indoor-outdoor pressure difference was controlled at 10, 30, and 50 Pa using a blower door depressurization procedure. Simultaneously, the air leakage characteristics of housing units are measured using the typical blower door pressurization-depressurization test method to correlate air leakage data and I/O ratios. As expected, moderately airtight housing units (ACH(50) <= 4.4) show lower I/O ratios than average leaky housing units (ACH(50) > 4.4); still, the averaged I/O ratios of finer sized particles (0.3-0.5, 0.5-1.0, and 1.0-3.0 mu m) in the moderately airtight housing units were 0.75, 0.59, and 0.61 at an I-O pressure difference of 50 Pa, and 0.62, 0.51, and 0.49 at 10 Pa. The study indicates that indoor residents in moderately airtight Korean multifamily housing units with relatively small envelope area can still be exposed to high concentrations of outdoor originated fine particles.
引用
收藏
页数:14
相关论文
empty
未找到相关数据