Unsymmetric Voltage of Conducted Noise Measurement System Without Grounding by Estimation of Ground Capacitance

被引:3
|
作者
Arai, Naruto [1 ,2 ]
Toriumi, Yohei [1 ]
Okamoto, Ken [3 ]
Kato, Jun [1 ]
Akiyama, Yoshiharu [4 ]
Sasaki, Ken [2 ]
机构
[1] NTT Corp, Space Environm & Energy Labs, Tokyo 1808585, Japan
[2] Univ Tokyo, Grad Sch Frontier Sci, Tokyo 2778563, Japan
[3] NTT Corp, Informat Network Lab Grp, Tokyo 1808585, Japan
[4] NTT Adv Technol Corp, Environm Business Unit, Tokyo 1808585, Japan
关键词
Capacitance measurement; conducted noise; unsymmetric voltage; voltage measurement; PERFORMANCE;
D O I
10.1109/TIM.2021.3053986
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Conducted noise originating from power supply equipment disrupts telecommunication networks, causing problems such as telecommunication interruptions and reduction in the speed of communication. Measurement of noise in data transmission lines at a repair site may require additional work to secure the electrical ground level for the measurement, because the data lines are differential pairs and the ground level is not always accessible. A method to estimate the capacitance between the measurement equipment and the ground was developed to allow measurement without access to the ground, i.e., in floating conditions. The method uses an oscillator and multiple electrodes to measure the capacitive coupling with the ground under the floor. A ground-capacitance-estimating device was fabricated and tested. Its accuracy was further improved by incorporating a linear function to express the relationship between the output of the device and the known ground capacitance in the calibration setting. This calibration procedure and the measurement procedure at the repair site are described. The noise voltage was calculated from the estimated ground capacitance and the voltage reading of the floating measurement equipment. The estimated ground capacitance was in the order of several tens of pF. The error of the corrected noise voltage was within 1.6 dB.
引用
收藏
页码:1 / 7
页数:7
相关论文
共 50 条
  • [1] Method of Measuring Conducted Noise Voltage with a Floating Measurement System to Ground
    Arai, Naruto
    Okamoto, Ken
    Kato, Jun
    Akiyama, Yoshiharu
    IEICE TRANSACTIONS ON COMMUNICATIONS, 2020, E103B (09) : 903 - 910
  • [2] Wearable Measurement Method for Voltage to Ground of Conducted Noise on Unshielded Cables
    Arai, Naruto
    Okamoto, Ken
    Kato, Jun
    PROCEEDINGS OF THE 2020 INTERNATIONAL SYMPOSIUM ON ELECTROMAGNETIC COMPATIBILITY (EMC EUROPE), 2020,
  • [3] A Novel Measuring Method of Capacitance to Ground in Resonant Grounding System
    Zhu Liang
    Liu Yuling
    Yang Qi
    Yu Kun
    Zeng Xiangjun
    Guo Tingting
    Yang Miao
    2018 CHINA INTERNATIONAL CONFERENCE ON ELECTRICITY DISTRIBUTION (CICED), 2018, : 1650 - 1653
  • [4] A Novel Unified Measurement Method for Ground Capacitance and Arc Suppression Coil Inductance of Resonant Grounding System
    Xie, Dawei
    Wang, Jingjing
    Zhu, Zhenggao
    Ding, Chao
    Wang, Lei
    Tian, Hongqiang
    Li, Shenghu
    2022 INTERNATIONAL CONFERENCE ON MECHANICAL ENGINEERING AND POWER ENGINEERING, MEPE, 2022, : 7 - 12
  • [5] Measurement of Capacitance Current of Neutral Point Non - grounding System
    Liu Hong
    Yu Hua
    Niu Shu
    Guo Ruizhou
    PROCEEDINGS OF 2018 IEEE 3RD ADVANCED INFORMATION TECHNOLOGY, ELECTRONIC AND AUTOMATION CONTROL CONFERENCE (IAEAC 2018), 2018, : 2393 - 2396
  • [6] Estimation of Deviation of Conducted Emission Measurement without LISN
    Li, Kang-Rong
    See, Kye-Yak
    2016 ASIA-PACIFIC INTERNATIONAL SYMPOSIUM ON ELECTROMAGNETIC COMPATIBILITY (APEMC), 2016, : 946 - 949
  • [7] Transmission line grounding capacitance estimation based on measurement transposition algorithm in EMS
    NARI-Relays Electrical Company Ltd., Nanjing 211100, China
    不详
    Dianli Xitong Zidonghue, 2007, 13 (63-66):
  • [8] Mode decomposition of conducted noise voltage with synchronized vector signal measurement
    Hayashi, Kei
    Mori, Shunji
    Ibuchi, Takaaki
    Funaki, Tsuyoshi
    IEICE COMMUNICATIONS EXPRESS, 2019, 8 (03): : 67 - 72
  • [9] Current measurement in electrical discharges in air gaps for conducted noise estimation
    Tellini, B
    Giannetti, R
    WHERE INSTRUMENTATION IS GOING - CONFERENCE PROCEEDINGS, VOLS 1 AND 2, 1998, : 749 - 751
  • [10] Using interpolation method to estimation step and touch voltage in grounding system
    Sikora, Roman
    Markiewicz, Przemyslaw
    Maczka, Mariusz
    Pawlowski, Stanislaw
    Plewako, Jolanta
    PRZEGLAD ELEKTROTECHNICZNY, 2023, 99 (02): : 263 - 266