A New Fault-Location Algorithm for Series-Compensated Double-Circuit Transmission Lines Based on the Distributed Parameter Model

被引:31
|
作者
Zhang, Ying [1 ]
Liang, Jun [1 ]
Yun, Zhihao [1 ]
Dong, Xiaoming [1 ]
机构
[1] Shandong Univ, Sch Elect Engn, Jinan 250100, Shandong, Peoples R China
关键词
Double-circuit transmission lines; series compensation; two terminals; six-sequence component; distributed parameter line model; DETECTION/LOCATION TECHNIQUE; CAPACITORS;
D O I
10.1109/TPWRD.2016.2626476
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A new two-terminal fault-location algorithm for series-compensated double-circuit transmission lines based on the distributed parameter line model is proposed. The system is considered as fully transposed, and a six-sequence component network is introduced to decouple the mutual electromagnetic effects between circuits. Two subroutines designated for the fault that occurs on the left or right side of the series compensator are developed. In each subroutine, the voltage of the series-compensated device is eliminated based on the fact that the sequence voltages calculated from two sides are equal at the fault point. The fault-location function is constructed by utilizing the feature in which the transition resistance is purely resistant at the fault point. The proposed algorithm does not rely on the equivalent model of a series-compensated device. Moreover, it does not require the fault type to be known, and there are no fault-location identification and pseudoroot elimination problems. PSCAD is employed to generate numerous fault cases in diverse conditions and the high accuracy of the proposed fault-location algorithm is validated in MATLAB.
引用
收藏
页码:2398 / 2407
页数:10
相关论文
共 50 条