Reliability data update method for emergency diesel generator of Daya Bay Nuclear Power Plant

被引:13
|
作者
Zubair, Muhammad [1 ]
Zhang Zhijian [1 ]
机构
[1] Harbin Engn Univ, Coll Nucl Sci & Technol, Harbin 150001, Heilongjiang, Peoples R China
关键词
Bayes' method; Calculation of parameters; Classical method; Failure rate estimation; Updating reliability data of EDG;
D O I
10.1016/j.anucene.2011.07.020
中图分类号
TL [原子能技术]; O571 [原子核物理学];
学科分类号
0827 ; 082701 ;
摘要
In the field of Living Probabilistic Safety Assessment (LPSA) the reliability data updating is an important factor. In risk analysis equipment failure data is needed to estimate the frequencies of events contributing to risk posed by a facility. Five years data of emergency diesel generator (EDG) of Daya Bay Nuclear Power Plant (NPP) has been studied in this paper. The data updating process has been done by using two methods, i.e., the classical method and Bayesian method. The aim of using these methods is to calculate the operational failure rate (A) and demand failure probability (p). The results show that the operational failure rate is 1.7E-3 per hour and the demand failure probability is 2.4E-2 demand per day for Daya Bay NPP. By comparing the results obtain from classical and Bayesian methods with EDF (Electric De France) it is concluded that the design and construction of Daya Bay NPP is very different than EDF therefore the reliability parameters used in Daya Bay NPP is based on the classical method. (C) 2011 Elsevier Ltd. All rights reserved.
引用
收藏
页码:2575 / 2580
页数:6
相关论文
共 50 条
  • [1] Reliability Data Update Method (RDUM) based on living PSA for emergency diesel generator of Daya Bay nuclear power plant
    Zubair, Muhammad
    Zhijian, Zhang
    SAFETY SCIENCE, 2013, 59 : 72 - 77
  • [2] DAYA BAY NUCLEAR POWER PLANT MAIN GENERATOR INNER STATOR REPLACEMENT
    Li Yujian
    Guo Zhenwu
    Lu Min
    PROCEEDINGS OF THE 25TH INTERNATIONAL CONFERENCE ON NUCLEAR ENGINEERING, 2017, VOL 1, 2017,
  • [3] The hunt for θ13 at the Daya Bay nuclear power plant
    Wang, Wei
    NEUTRINO FACTORIES, SUPERBEAMS, AND BETA BEAMS, 2010, 1222 : 494 - 497
  • [5] Refueling outage technique of Daya Bay Nuclear Power Plant
    Ding, Zhen-Xing
    Zhongguo Dianli/Electric Power, 2002, 35 (05):
  • [6] PERIODIC TESTS IMPROVEMENT OF EMERGENCY DIESEL GENERATOR UNITS IN NUCLEAR POWER PLANT
    Fei, Liu
    PROCEEDINGS OF THE 2020 INTERNATIONAL CONFERENCE ON NUCLEAR ENGINEERING (ICONE2020), VOL 2, 2020,
  • [7] Research on Improvement of Pilot Solenoid Valve for Emergency Diesel Generator in Nuclear Power Plant
    Fu J.
    Zhang L.
    Tao G.
    Xiang F.
    Liu S.
    Chu X.
    Wang X.
    Yin Y.
    Hedongli Gongcheng/Nuclear Power Engineering, 2023, 44 (06): : 226 - 230
  • [8] A performance assessment of a base isolation system for an Emergency Diesel Generator in a nuclear power plant
    Choun, Young-Sun
    Kim, Min-Kyu
    NUCLEAR ENGINEERING AND TECHNOLOGY, 2008, 40 (04) : 285 - 298
  • [9] Empirical bayes estimation of the reliability of nuclear-power-plant emergency diesel generators
    Martz, HF
    Kvam, PH
    Abramson, LR
    TECHNOMETRICS, 1996, 38 (01) : 11 - 24