Numerical investigation of long-term operation of ground-source heat pumps at neighborhood level: Focus on thermal interactions and electricity consumption

被引:3
|
作者
Jaafar, Mohamad Ali [1 ]
Maragna, Charles [1 ]
机构
[1] BRGM Geol & Min Res Bur, Geothermal Dept, 3 Ave Claude Guillemin, F-45100 Orleans, France
关键词
Shallow geothermal energy; Ground-source heat pumps; Line source models; Long-term performance; Electrical consumption; Sustainable cities; EXCHANGERS; SIMULATION; PERFORMANCE; SYSTEMS; DESIGN; MODELS; FIELD; FLOW;
D O I
10.1016/j.geothermics.2021.102172
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
A comprehensive numerical investigation of long-term operation of Ground-Sourced Heat Pumps through Borehole Heat Exchangers is presented. Thermal fluxes between systems are analyzed through a semi-analytical method based on line source models. Operation points of geothermal and backup systems are determined by an hourly-based non-linear constrained optimization. Simulations of a 12-buildings neighborhood demonstrated that middle-buildings experience higher electrical consumptions than corner-buildings. Thermal interactions could be interferences or synergies decreasing or increasing GSHP performances, respectively, depending mainly on heating/cooling balance. Parametrical study showed that low Darcy velocities, insulated ground surface, shorter heat-exchangers, and denser and compact neighborhoods enhance thermal interactions impacts.
引用
收藏
页数:13
相关论文
共 25 条
  • [1] Impact of long-term operation of ground-source heat pump on subsurface thermal state in urban areas
    Choi, Wonjun
    Ooka, Ryozo
    Nam, Yujin
    SUSTAINABLE CITIES AND SOCIETY, 2018, 38 : 429 - 439
  • [2] Long-term monitoring and performance of ground source heat pumps
    Stafford, A.
    BUILDING RESEARCH AND INFORMATION, 2011, 39 (06): : 566 - 573
  • [3] Impact of grout thermal conductivity on the long-term efficiency ofthe ground-source heat pump systemTomislav
    Kurevija, Tomislav
    Macenic, Marija
    Borovic, Stasa
    SUSTAINABLE CITIES AND SOCIETY, 2017, 31 : 1 - 11
  • [4] The Long-Term Mitigating Effect of Horizontal Ground-Source Heat Exchangers on Permafrost Thaw Settlement
    Gheisari, Amir Fatollahzadeh
    Maghoul, Pooneh
    Hollander, Hartmut M.
    Kenyon, Rob
    Sinclair, Rob
    Saaly, Maryam
    PROCESSES, 2021, 9 (09)
  • [5] Forecast and analysis of long-term operation of ground source heat pump system
    Qi, Zi-Shu
    Gao, Qing
    Yu, Ming
    Liu, Yan
    Bai, Li
    Jilin Daxue Xuebao (Gongxueban)/Journal of Jilin University (Engineering and Technology Edition), 2012, 42 (04): : 877 - 881
  • [6] Long-term operation analysis of a ground source heat pump with an air source heat pump as an auxiliary heat source in a warm region
    Kaneko, Chika
    Yoshinaga, Mika
    ENERGY AND BUILDINGS, 2023, 289
  • [7] Effects of Electric Vehicles and Heat Pumps on Long-term Electricity Consumption Scenarios for Rural Areas in the Nordic Environment
    Haakana, Juha
    Haapaniemi, Jouni
    Lassila, Jukka
    Partanen, Jarmo
    Niska, Harri
    Rautiainen, Antti
    2018 15TH INTERNATIONAL CONFERENCE ON THE EUROPEAN ENERGY MARKET (EEM), 2018,
  • [8] Numerical investigation of the long-term thermal performance of a novel thermo-active foundation pile coupled with a ground source heat pump in a cold-climate
    Jathunge, Charaka Beragama
    Darbandi, Amirhossein
    Dworkin, Seth B.
    Mwesigye, Aggrey
    ENERGY, 2024, 292
  • [9] Effect of borehole short-time-step performance on long-term dynamic simulation of ground-source heat pump system
    Lee, C. K.
    ENERGY AND BUILDINGS, 2016, 129 : 238 - 246
  • [10] Long-term heating and cooling pattern extraction method and multi-case analysis of ground-source heat pump systems
    Zhang S.
    Zhang L.
    Zhang X.
    Dongnan Daxue Xuebao (Ziran Kexue Ban)/Journal of Southeast University (Natural Science Edition), 2022, 52 (01): : 9 - 15