VOLTAGE CONTROL FOR THREE-PHASE UPS INVERTER USING P plus RESONANT CONTROLLERS

被引:0
|
作者
Caicedo, Jorge [1 ]
Aredes, Mauricio [1 ]
机构
[1] COPPE UFRJ, Rio De Janeiro, RJ, Brazil
关键词
Control design; DC-AC power converters; Inverters; Pulse width modulation converters; Uninterruptible power systems; Voltage control; PREDICTIVE CONTROL;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This paper introduces a voltage-control strategy using proportional plus resonant controllers and current-filter-feedback. It also presents two harmonic-compensator topologies, and an analytical methodology to calculate the controller parameters. Furthermore, simulation and experimental results of a 3.6 kVA prototype validated the theoretical assumptions. Main results shown a three-phase inverter with a settling-time of 33 ms, up to 1.8% voltage THD under nonlinear load, and less than 15% output-voltage disturbances under full-rated load. These outcomes verified the effectiveness of the proposed control-strategy and accomplished the IEC62040-3 and IEEE519 international standards.
引用
收藏
页数:6
相关论文
共 50 条
  • [1] Digital voltage and current controllers for three-phase PWM inverter for UPS applications
    Botterón, F
    Pinheiro, H
    Gründling, HA
    Pinheiro, JR
    Hey, HL
    CONFERENCE RECORD OF THE 2001 IEEE INDUSTRY APPLICATIONS CONFERENCE, VOLS 1-4, 2001, : 2667 - 2674
  • [2] Inverter output voltage control of three-phase UPS systems using feedback linearization
    Kim, Dong-Eok
    Lee, Dong-Choon
    IECON 2007: 33RD ANNUAL CONFERENCE OF THE IEEE INDUSTRIAL ELECTRONICS SOCIETY, VOLS 1-3, CONFERENCE PROCEEDINGS, 2007, : 1737 - 1742
  • [3] Robust Control Design of Multiple Resonant Controllers Applied to Three-Phase UPS Inverter Under Unbalanced and Nonlinear Loads
    Barden, Alisson Thomas
    Alves Pereira, Luis Fernando
    IECON 2015 - 41ST ANNUAL CONFERENCE OF THE IEEE INDUSTRIAL ELECTRONICS SOCIETY, 2015, : 1483 - 1488
  • [4] A Multiple Resonant Based on Reference Feedforward Adaptive Voltage Control of Three-Phase Inverter
    Huang R.
    Quan X.
    Wu Z.
    Hu Q.
    Li S.
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2022, 37 (16): : 4212 - 4224
  • [5] Improved Design and Control of Proportional Resonant Controller for Three-Phase Voltage Source Inverter
    Ebad, Mehdi
    Song, Byeong-Mun
    2012 IEEE POWER ELECTRONICS AND MACHINES IN WIND APPLICATIONS (PEMWA), 2012,
  • [6] Feedback Linearization Control of Three-Phase UPS Inverter Systems
    Kim, Dong-Eok
    Lee, Dong-Choon
    IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2010, 57 (03) : 963 - 968
  • [7] Optimal control of three-phase PWM inverter for UPS systems
    Jung, JW
    Dai, M
    Keyhani, A
    PESC 04: 2004 IEEE 35TH ANNUAL POWER ELECTRONICS SPECIALISTS CONFERENCE, VOLS 1-6, CONFERENCE PROCEEDINGS, 2004, : 2054 - 2059
  • [8] Ultra fast voltage control for three-phase UPS
    Moreau, R
    Le Claire, JC
    IPEMC 2004: THE 4TH INTERNATIONAL POWER ELECTRONICS AND MOTION CONTROL CONFERENCE, VOLS 1-3, CONFERENCE PROCEEDINGS, 2004, : 977 - 982
  • [9] DSP control of three-phase voltage source UPS inverter with software controlled harmonic conditioners
    Byun, YB
    Joe, KY
    Park, SJ
    Kim, CU
    INTELEC 97 - 19TH INTERNATIONAL TELECOMMUNICATIONS ENERGY CONFERENCE, PROCEEDINGS: POWER AND ENERGY SYSTEMS IN CONVERGING MARKETS, 1997, : 195 - 200
  • [10] Output voltage control of a four-leg inverter based three-phase UPS utilizing stationary frame resonant filter banks
    Hava, Ahmet M.
    Demirkutlu, Eyyup
    2007 EUROPEAN CONFERENCE ON POWER ELECTRONICS AND APPLICATIONS, VOLS 1-10, 2007, : 4925 - 4934