RACK-LEVEL THERMOSYPHON COOLING AND VAPOR-COMPRESSION DRIVEN HEAT RECOVERY: EVAPORATOR MODEL

被引:0
|
作者
Khalid, Rehan [1 ]
Amalfi, Raffaele Luca [2 ]
Wemhoff, Aaron P. [1 ]
机构
[1] Villanova Univ, Dept Mech Engn, 800 Lancaster Ave, Villanova, PA 19085 USA
[2] Nokia Bell Labs, Thermal Management Grp, 600-700 Mt Ave, Murray Hill, NJ 07974 USA
关键词
Analytical modeling; Data centers; Electronics cooling; Liquid-cooling; Mathematical modeling; Modeling; GENERAL CORRELATION; 2-PHASE FLOW; PUMP; SYSTEM;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
An in-rack cooling system connected to an external vapor recompression loop can be an economical solution to harness waste heat recovery in data centers. Validated subsystem-level models of the thermosyphon cooling and recompression loops (evaporator, heat exchangers, compressor, etc.) are needed to predict overall system performance and to perform design optimization based on the operating conditions. This paper specifically focuses on the model of the evaporator, which is a finned-tube heat exchanger incorporated in a thermosyphon cooling loop. The fin packis divided into individual segments to analyze the refrigerant and air side heat fransfer characteristics. Refrigerant flow in the tubes is modeled as 1-D flow scheme with fransport equations solved on a staggered grid. The air side is modeled using differential equations to represent the air temperature and humidity ratio and to predict if moisture removal will occur, in which case the airside heat transfer coefficient is suitably reduced. The louver fins are modeled as individual hexagons and are treated in conjunction with the tube walls. A segment-by-segment approach is utilized for each tube and the heat exchanger geometry is subsequently evaluated from one end to the other, with air property changes considered for each subsequent row of tubes. Model predictions of stream outlet temperature and pressure, refrigerant outlet vapor quality and heat exchanger duty show good agreement when compared against a commercial software.
引用
收藏
页数:12
相关论文
共 22 条
  • [1] RACK-LEVEL THERMOSYPHON COOLING AND VAPOR-COMPRESSION DRIVEN HEAT RECOVERY: COMPRESSOR MODEL
    Khalid, Rehan
    Amalfi, Raffaele Luca
    Wemhoff, Aaron P.
    PROCEEDINGS OF ASME 2021 INTERNATIONAL TECHNICAL CONFERENCE AND EXHIBITION ON PACKAGING AND INTEGRATION OF ELECTRONIC AND PHOTONIC MICROSYSTEMS (INTERPACK2021), 2021,
  • [2] RACK-LEVEL THERMOSYPHON COOLING AND VAPOR-COMPRESSION DRIVEN HEAT RECOVERY: CONDENSER MODEL
    Khalid, Rehan
    Amalfi, Raffaele Luca
    Wemhoff, Aaron P.
    PROCEEDINGS OF ASME 2021 INTERNATIONAL TECHNICAL CONFERENCE AND EXHIBITION ON PACKAGING AND INTEGRATION OF ELECTRONIC AND PHOTONIC MICROSYSTEMS (INTERPACK2021), 2021,
  • [3] Characterization of a Rack-Level Thermosyphon-Based Cooling System
    Khalid, R.
    Schon, S. G.
    Amalfi, R. L.
    Ortega, A.
    Wemhoff, A. P.
    JOURNAL OF ELECTRONIC PACKAGING, 2024, 146 (03)
  • [4] Experimental study on a novel pump-driven heat pipe/vapor compression system for rack-level cooling of data centers
    Sun, Xiaoqing
    Zhang, Ce
    Han, Zongwei
    Dong, Jiaxiang
    Zhang, Yiqi
    Li, Mengyi
    Li, Xiuming
    Wang, Qinghai
    Wen, Zhenwu
    Zheng, Baoli
    ENERGY, 2023, 274
  • [5] Validation and Application of a Finned Tube Heat Exchanger Model for Rack-Level Cooling
    Khalid, R.
    Youssef, E.
    Amalfi, R. L.
    Ortega, A.
    Wemhoff, A. P.
    JOURNAL OF ELECTRONIC PACKAGING, 2024, 146 (02)
  • [6] Wearable engine-driven vapor-compression cooling system for elevated ambients
    Ernst, Timothy C.
    Garimella, Srinivas
    PROCEEDINGS OF THE ASME INTERNATIONAL MECHANICAL ENGINEERING CONGRESS AND EXPOSITION 2007, VOL 15: SUSTAINABLE PRODUCTS AND PROCESSES, 2008, : 79 - 92
  • [7] Optimization of Evaporator for a Vapor Compression Cooling System for High Heat Flux CPU
    Kim, Seon-Chang
    Jeon, Dong-Soon
    Kim, Young-Lyoul
    TRANSACTIONS OF THE KOREAN SOCIETY OF MECHANICAL ENGINEERS B, 2008, 32 (04) : 255 - 265
  • [8] MODEL BASED ANALYSIS OF AN INTEGRATED SYSTEM OF VAPOR-COMPRESSION CHILLER AND ABSORPTION HEAT PUMP
    Kung, Yi-Shu
    Qu, Ming
    Peng, Steve
    PROCEEDINGS OF THE ASME 7TH INTERNATIONAL CONFERENCE ON ENERGY SUSTAINABILITY, 2013, 2014,
  • [9] Waste heat driven absorption/vapor-compression cascade refrigeration system for megawatt scale, high-flux, low-temperature cooling
    Garimella, Srinivas
    Brown, Ashlie M.
    Nagavarapu, Ananda Krishna
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2011, 34 (08): : 1776 - 1785
  • [10] THE MECHANICALLY DRIVEN HEAT-RECOVERY SYSTEM OF VAPOR COMPRESSION DESALTERS
    DARWISH, MA
    ABDELJAWAD, M
    ELHADEK, A
    HEAT RECOVERY SYSTEMS & CHP, 1990, 10 (5-6): : 447 - 456