Sliding-Mode-Based Direct Power Control of Grid-Connected Wind-Turbine-Driven Doubly Fed Induction Generators Under Unbalanced Grid Voltage Conditions

被引:156
|
作者
Shang, Lei [1 ,2 ]
Hu, Jiabing [3 ]
机构
[1] Nari Relays Elect Co Ltd, Nanjing 211100, Jiangsu, Peoples R China
[2] Huazhong Univ Sci & Technol, Coll Elect & Elect Engn, Wuhan 430074, Peoples R China
[3] State Key Lab Adv Electromagnet Engn & Technol, Wuhan 430074, Peoples R China
基金
中国国家自然科学基金;
关键词
Direct power control (DPC); doubly fed induction generator (DFIG); power compensation; sliding mode control (SMC); unbalanced grid voltage; wind turbine; DIRECT TORQUE CONTROL; SWITCHING FREQUENCY; DFIG; CONVERTERS; MACHINE; SYSTEMS; RIPPLE;
D O I
10.1109/TEC.2011.2180389
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This paper proposes an improved direct power control (DPC) strategy of grid-connected wind-turbine-driven doubly fed induction generators (DFIGs) when the grid voltage is unbalanced. The DPC scheme is based on the sliding mode control (SMC) approach, which directly regulates the instantaneous active and reactive powers in the stator stationary reference frame without the requirement of either synchronous coordinate transformation or phase angle tracking of grid voltage. The behavior of DFIGs by the conventional SMC-DPC, which takes no negative-sequence voltage into consideration, is analyzed under unbalanced grid voltage conditions. A novel power compensation method is proposed for the SMC-based DPC during network unbalance to achieve three selective control targets, i.e., obtaining sinusoidal and symmetrical stator current, removing stator interchanging reactive power ripples and canceling stator output active power oscillations, respectively. The active and reactive power compensation components are calculated via a simple method and the proposed three control targets can be achieved, respectively, without the need of extracting negative-sequence stator current components. Experimental results on a 2kW DFIG prototype are presented to verify the correctness and validity of the proposed control strategy and power compensation method.
引用
收藏
页码:362 / 373
页数:12
相关论文
共 50 条
  • [1] A comprehensive review of LVRT capability and sliding mode control of grid-connected wind-turbine-driven doubly fed induction generator
    Kerrouche, K. D. E.
    Mezouar, A.
    Boumediene, L.
    Van den Bossche, A.
    AUTOMATIKA, 2016, 57 (04) : 922 - 935
  • [2] Sliding-mode-based direct power control of grid-connected voltage-sourced inverters under unbalanced network conditions
    Shang, L.
    Sun, D.
    Hu, J.
    IET POWER ELECTRONICS, 2011, 4 (05) : 570 - 579
  • [3] Integral Sliding-Mode Direct Torque Control of Doubly-Fed Induction Generators Under Unbalanced Grid Voltage
    Chen, Si Zhe
    Cheung, Norbert C.
    Wong, Ka Chung
    Wu, Jie
    IEEE TRANSACTIONS ON ENERGY CONVERSION, 2010, 25 (02) : 356 - 368
  • [4] A Novel Control Strategy for Operating Grid Connected Doubly Fed Induction Generators Under Unbalanced Grid Voltage
    Nithin, A. N.
    Samina, T.
    Ramaiyer, S.
    Beevi, Bishath A.
    2015 INTERNATIONAL CONFERENCE ON CONTROL COMMUNICATION & COMPUTING INDIA (ICCC), 2015, : 218 - 223
  • [5] Predictive Direct Power Control of Doubly Fed Induction Generators Under Unbalanced Grid Voltage Conditions for Power Quality Improvement
    Hu, Jiefeng
    Zhu, Jianguo
    Dorrell, David G.
    IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, 2015, 6 (03) : 943 - 950
  • [6] Control of a doubly fed induction wind generator under unbalanced grid voltage conditions
    Brekken, Ted K. A.
    Mohan, Ned
    IEEE TRANSACTIONS ON ENERGY CONVERSION, 2007, 22 (01) : 129 - 135
  • [7] Active and Reactive Power Control of Doubly Fed Induction Generators for Wind Energy Generation under Unbalanced Grid Voltage Conditions
    Shehata, E. G.
    ELECTRIC POWER COMPONENTS AND SYSTEMS, 2013, 41 (06) : 619 - 640
  • [8] Reactive power optimal control of doubly fed induction wind generators under unbalanced grid voltage swell
    School of Electrical Engineering and Automation, Hefei University of Technology, Heifei
    Anhui Province
    230009, China
    Zhongguo Dianji Gongcheng Xuebao, 13 (3211-3220):
  • [9] Modeling and control of wind-turbine driven doubly-fed induction generators under harmonic grid voltage conditions
    Xu, Hailiang
    Hu, Jiabing
    He, Yikang
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2011, 35 (11): : 20 - 26
  • [10] Direct Power Control Applied to Doubly Fed Induction Generator Under Unbalanced Grid Voltage Conditions
    Santos-Martin, David
    Rodriguez-Amenedo, Jose Luis
    Arnalte, Santiago
    IEEE TRANSACTIONS ON POWER ELECTRONICS, 2008, 23 (05) : 2328 - 2336