Comparison study of air mixing modes in liquid desiccant based all-air air conditioning systems

被引:3
|
作者
Xiao, Fu [1 ]
Niu, XiaoFeng [1 ]
机构
[1] Hong Kong Polytech Univ, Dept Bldg Serv Engn, Hong Kong, Hong Kong, Peoples R China
关键词
PERFORMANCE; DEHUMIDIFICATION;
D O I
10.1177/0143624411418183
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Liquid desiccant is an energy-saving, environmentally friendly and healthy means of air dehumidification. A liquid desiccant-based all-air air conditioning system is studied by simulation. Two different modes of air mixing between the return air and the fresh air are compared, that is mixing before and mixing after the liquid desiccant dehumidifier, respectively. System performance and total energy consumption of the two modes under different operation conditions are obtained. The results show that mixing air after dehumidification consumes less energy than mixing air before dehumidification. Coefficient of performance (COP) of the all-air system with air mixing after dehumidification is higher. The differences of COP and energy consumption between the two air mixing modes increase when the outdoor air temperature and relative humidity increase.
引用
收藏
页码:423 / 435
页数:13
相关论文
共 50 条
  • [1] PERFORMANCE ANALYSIS ON THE DIFFERENT AIR MIXING MODES OF LIQUID DESICCANT BASED AIR CONDITIONING SYSTEM
    Niu, X. F.
    Xiao, F.
    Wang, S. W.
    PROCEEDINGS OF THE FIRST INTERNATIONAL CONFERENCE ON SUSTAINABLE URBANIZATION (ICSU 2010), 2010, : 1839 - 1847
  • [2] ALL-AIR SYSTEMS
    GARBER, MM
    ASHRAE JOURNAL, 1970, 12 (06): : 47 - &
  • [3] TAB OF ALL-AIR SYSTEMS
    WRAY, HL
    ASHRAE JOURNAL, 1970, 12 (06): : 48 - &
  • [4] Survey of hybrid liquid desiccant air conditioning systems
    Mohammad, Abdulrahman Th.
    Bin Mat, Sohif
    Sulaiman, M. Y.
    Sopian, K.
    Al-abidi, Abduljalil A.
    RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2013, 20 : 186 - 200
  • [5] Comparison of desiccant air conditioning systems with different indirect evaporative air coolers
    Pandelidis, Demis
    Anisimov, Sergey
    Worek, William M.
    Drag, Pawel
    ENERGY CONVERSION AND MANAGEMENT, 2016, 117 : 375 - 392
  • [6] Study on Solar Liquid Desiccant Air-conditioning Systems in Xiamen
    Hong, Xiaoqiang
    Li, Li
    He, Wenqiong
    Ge, Yuxiao
    Xu, Siwei
    10TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATION AND AIR CONDITIONING, ISHVAC2017, 2017, 205 : 2807 - 2814
  • [7] Experimental study on air change effectiveness: Improving air distribution with all-air heating systems
    Amai, Hideyuki
    Liu, Shichao
    Novoselac, Atila
    BUILDING AND ENVIRONMENT, 2017, 125 : 515 - 527
  • [8] Principles for design of all-air systems
    Jönsson, A
    PROCEEDINGS OF THE 4TH INTERNATIONAL CONFERENCE ON INDOOR AIR QUALITY, VENTILATION AND ENERGY CONSERVATION IN BUILDINGS, VOLS I-III, 2001, : 1129 - 1136
  • [9] All-air systems (TC 9.1)
    ASHRAE Handb, (qq):
  • [10] AN ALL-AIR AIR-CARGO SYSTEM
    FOSTER, HE
    ASTRONAUTICS & AERONAUTICS, 1969, 7 (09): : 79 - &