Modeling Type-4 Wind in Weak Grids

被引:133
作者
Fan, Lingling [1 ]
机构
[1] Univ S Florida, Dept Elect Engn, Tampa, FL 33420 USA
关键词
Wind power plants; low-frequency oscillations; weak grids; phase-locked loop (PLL); linear system analysis; STABILITY; CONVERTERS; DYNAMICS; TURBINES; FAULTS;
D O I
10.1109/TSTE.2018.2849849
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
An existing wind power plant at ERCOT experienced poorly damped and undamped low-frequency oscillations at 3 similar to 4 Hz under weak grid condition. The objective of this paper is to shed the insight of the oscillation mechanism through linear system analysis. Two simplified models are developed and compared against a detailed model for Type-4 wind with weak grid interconnection. The detailed model includes grid-side converter's outer power/voltage control, inner current controls, phase-locked loop (PLL), and transmission line electromagnetic dynamics. The first simplified model uses a first-order delay to replace the current control loop and ignores the transmission line dynamics and PLL. The second simplified model uses the same assumptions except that PLL is considered. Linearized system block diagrams for the two simplified models are derived and compared. The mechanism of the low-frequency oscillations are explained using eigenvalue analysis and the Root-Locus method. The root causes are identified as weak grid, high wind power export, low voltage, and low PLL bandwidth. Further, the simplified model considering PLL dynamics is more accurate in low-frequency oscillation mode identification and system stability prediction.
引用
收藏
页码:853 / 864
页数:12
相关论文
共 22 条
[1]  
Amin M., 2015, P 11 IET INT C AC DC, P1
[2]  
[Anonymous], 2012, CONTROL ELECT DRIVES
[3]  
[Anonymous], 2017, CONTROL DYNAMICS POW
[4]  
[Anonymous], 2012, 2012 IEEE POW EN SOC
[5]  
[Anonymous], 2015, P 11 IET INT C AC DC
[6]  
[Anonymous], 2013, SENSORS 2013 IEEE, DOI [DOI 10.1109/ICSENS.2013.6688408, 10.1109/ICSENS.2013.6688408]
[7]   Impedance Modeling and Analysis of Grid-Connected Voltage-Source Converters [J].
Cespedes, Mauricio ;
Sun, Jian .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2014, 29 (03) :1254-1261
[8]   Analysis of Phase-Locked Loop Low-Frequency Stability in Three-Phase Grid-Connected Power Converters Considering Impedance Interactions [J].
Dong, Dong ;
Wen, Bo ;
Boroyevich, Dushan ;
Mattavelli, Paolo ;
Xue, Yaosuo .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2015, 62 (01) :310-321
[9]   An Explanation of Oscillations Due to Wind Power Plants Weak Grid Interconnection [J].
Fan, Lingling ;
Miao, Zhixin .
IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, 2018, 9 (01) :488-490
[10]   Instability of Wind Turbine Converters During Current Injection to Low Voltage Grid Faults and PLL Frequency Based Stability Solution [J].
Goksu, Omer ;
Teodorescu, Remus ;
Bak, Claus Leth ;
Iov, Florin ;
Kjaer, Philip Carne .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2014, 29 (04) :1683-1691