Investigating the effect of cavity size within medium-voltage power cable on partial discharge behaviour

被引:32
|
作者
Gouda, Osama E. [1 ]
ElFarskoury, Adel A. [2 ]
Elsinnary, Abd Rabu [3 ]
Farag, Adel A. [4 ]
机构
[1] Cairo Univ, Elect Power Dept, Fac Engn, Giza, Egypt
[2] Extra High Voltage Res Ctr, Cairo, Egypt
[3] Al Azhar Univ, Elect Power Dept, Fac Engn, Cairo, Egypt
[4] South Cairo Elect Distribut Co, Cairo, Egypt
关键词
XLPE insulation; power cable insulation; partial discharges; cavity size; medium-voltage power cable; partial discharge behaviour; cross-linked polyethylene insulation ageing; XLPE insulation ageing; partial discharge activity; PD activity; artificial spherical cavity depths; 2D model geometry; COMSOL software; MATLAB program; PD measurements; PD inception voltage; PD magnitude; DIELECTRIC MATERIAL; SPHERICAL CAVITY; SIMULATION; INSULATION; FREQUENCY; MODEL;
D O I
10.1049/iet-gtd.2017.1012
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
One of the common causes of cross-linked polyethylene (XLPE) insulation ageing and finally cable failure is the presence of a cavity within cable insulation. Gas filled cavities can be initiated in XLPE cables during its manufacturing, installing and operating conditions. Once the size of the cavity reaches the critical limit, noticeable partial discharge (PD) activity develops. Therefore, the size of the cavity is one of the important factors that considered when investigating the PD activity in power cable. This work studies the effect of cavity size on PD behaviour within insulation layer of an 18/30kV XLPE cable specimen; the changing in an artificial spherical cavity depths and diameters is investigated in the laboratory. In addition, 2D model geometry of a cable insulation having an artificial cavity is also developed using COMSOL software and MATLAB program to simulate the PD measurements from the laboratory experiments to imitate the conditions found during measurements, hence interpreting the obtained experimental results and determining the significant parameters influencing PD activity; hence, more a fuller understanding of PD phenomena within a cavity. The results show good coincidence between experimental and simulated data, in terms of PD magnitude and PD inception voltage.
引用
收藏
页码:1190 / 1197
页数:8
相关论文
共 50 条
  • [1] Investigating the Effect of Frequency and Wave Shape of Voltage Source on Partial Discharge Behaviour within Cavity in Medium Voltage Cable
    Gouda, Osama
    ElFaraskoury, Adel
    ElSinary, AbdRabu
    Farag, Adel
    2017 NINETEENTH INTERNATIONAL MIDDLE-EAST POWER SYSTEMS CONFERENCE (MEPCON), 2017, : 1093 - 1099
  • [2] Simulation of Partial Discharge Location in Medium-Voltage Power Cables
    Liang, Keng-Wei
    Lee, Chang-Hsing
    Chiu, Min-Yen
    Fan, Chen-Li
    Yu-Chih
    Lin
    PROCEEDINGS OF 2012 IEEE INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS (IEEE CMD 2012), 2012, : 655 - 658
  • [3] HOW TO TROUBLESHOOT MEDIUM-VOLTAGE POWER CABLE
    OATESS, CJ
    IEEE TRANSACTIONS ON INDUSTRY AND GENERAL APPLICATIONS, 1969, IGA5 (02): : 163 - &
  • [4] SPLICING AND TERMINATING MEDIUM-VOLTAGE POWER CABLE
    PALKO, E
    PLANT ENGINEERING, 1984, 38 (08) : 62 - 69
  • [5] Partial discharge diagnosis and monitoring of medium-voltage substations
    Hribernik, W.
    Berger, K.
    Pascoli, G.
    ELEKTROTECHNIK UND INFORMATIONSTECHNIK, 2007, 124 (12): : 430 - 434
  • [6] Partial discharge diagnostics of long and branched medium-voltage cables
    Steennis, EF
    Ross, R
    van Schaik, N
    Boone, W
    van Aartrijk, DM
    ICSD '01: PROCEEDINGS OF THE 2001 IEEE 7TH INTERNATIONAL CONFERENCE ON SOLID DIELECTRICS, 2001, : 27 - 30
  • [7] Numerical Modeling of Partial Discharge in a Void Cavity Within High-Voltage Cable Insulation
    Algwari, Qais Th
    Saleh, Dawood N.
    IEEE TRANSACTIONS ON PLASMA SCIENCE, 2021, 49 (05) : 1536 - 1542
  • [8] Analytic calculation of partial discharge threshold in a gaseous cavity within high voltage cable insulation
    Boudiaf, A.
    Bouazabia, S.
    Harid, N.
    Amrani, M. L.
    ELECTRICAL ENGINEERING, 2022, 104 (02) : 555 - 565
  • [9] Analytic calculation of partial discharge threshold in a gaseous cavity within high voltage cable insulation
    A. Boudiaf
    S. Bouazabia
    N. Harid
    M. L. Amrani
    Electrical Engineering, 2022, 104 : 555 - 565
  • [10] Real On-Site Partial Discharge Measurement Technique in Medium Voltage Power Cable
    Abdullah, A. Z.
    Rohani, M. N. K. H.
    Isa, M.
    Hamid, H.
    Arshad, S. N. M.
    Othman, M.
    2018 IEEE 7TH INTERNATIONAL CONFERENCE ON POWER AND ENERGY (PECON), 2018, : 405 - 408