On-line model-based performance monitoring of a shell-and-tube type heat exchanger using steam and water

被引:12
作者
Wakui, Tetsuya [1 ]
Yokoyama, Ryohei [1 ]
机构
[1] Osaka Prefecture Univ, Dept Mech Engn, Naka Ku, Osaka 5998531, Japan
关键词
model-based monitoring and diagnostic; heat exchanger; heat exchange performance; heat transfer model;
D O I
10.1016/j.enconman.2008.04.009
中图分类号
O414.1 [热力学];
学科分类号
摘要
The on-line performance monitoring of a shell-and-tube type heat exchanger using steam and water, which is one of the key components of distributed energy supply systems, has been developed on the basis of a theoretical model. In this on-line performance monitoring, output process variables and performance of the heat exchanger in response to the variation in measured input process variables are first estimated by using its steady-state model. These estimated values are then compared with the measured ones. Its effectiveness has been confirmed by the demonstration experiments conducted not only in the steady and transient states but also under the condition of air accumulation in the shell as one of the common failures of this type of heat exchanger. The results confirm the sufficient accuracy of estimating the output process variables and heat exchange performance in a wide operating range, and the capability of detecting the deterioration of the heat exchange performance due to the air accumulation in a short period. (C) 2008 Elsevier Ltd. All rights reserved.
引用
收藏
页码:2669 / 2677
页数:9
相关论文
共 18 条
[1]   Automatic diagnostics and prognostics of energy conversion processes via knowledge-based systems [J].
Biagetti, T ;
Sciubba, E .
ENERGY, 2004, 29 (12-15) :2553-2572
[2]   Transient pattern analysis for fault detection and diagnosis of HVAC systems [J].
Cho, SH ;
Yang, HC ;
Zaheer-uddin, M ;
Ahn, BC .
ENERGY CONVERSION AND MANAGEMENT, 2005, 46 (18-19) :3103-3116
[3]   Detection and diagnosis for sensor fault in HVAC systems [J].
Du, Zhimin ;
Jin, Xinqiao .
ENERGY CONVERSION AND MANAGEMENT, 2007, 48 (03) :693-702
[4]  
EINO J, 2005, P 18 INT C COND MON, P113
[5]   Data mining based sensor fault diagnosis and validation for building air conditioning system [J].
Hou, Zhijian ;
Lian, Zhiwei ;
Yao, Ye ;
Yuan, Xinjian .
ENERGY CONVERSION AND MANAGEMENT, 2006, 47 (15-16) :2479-2490
[6]  
INCROPERA FP, 2002, FUNDAMENTALS HEAT MA, P496
[7]  
*JAP SOC MATH ENG, 1986, JSME DAT BOOK HEAT T, P147
[8]   Implementation of on-line performance monitoring system at Seoincheon and Sinincheon combined cycle power plant [J].
Kim, SM ;
Joo, YJ .
ENERGY, 2005, 30 (13) :2383-2401
[9]  
*PROPATH GROUP, 2001, PROPATH PROGR PACK T
[10]   Structural theory and thermoeconomic diagnosis Part 1. On malfunction and dysfunction analysis [J].
Torres, C ;
Valero, A ;
Serra, L ;
Royo, J .
ENERGY CONVERSION AND MANAGEMENT, 2002, 43 (9-12) :1503-1518