Fire accident investigation of an explosion caused by static electricity in a propylene plant

被引:19
|
作者
Chou, Hung-Cheng [1 ]
Yeh, Chi-Tang [1 ]
Shu, Chi-Min [2 ]
机构
[1] Natl Yunlin Univ Sci & Technol YunTech, Grad Sch Engn Sci & Technol, Doctoral Program, Touliu 64002, Yunlin, Taiwan
[2] Natl Yunlin Univ Sci & Technol, Dept Safety Hlth & Environm Engn, Touliu 64002, Yunlin, Taiwan
关键词
Fire and explosion; Liquid acetone leakage; Acetone storage tank; Burning (bursting) loss; Static electricity; Flammable liquids;
D O I
10.1016/j.psep.2015.02.007
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
This study investigated a 2010 fire and explosion that occurred at a polypropylene (PP) and copper-clad laminate high-tech plant in Taiwan. Liquid acetone leakage caused the fire and explosion. One person was killed and five were injured; property damage was estimated at US$20 million. In contrast to conventional plants, high-tech plants have sophisticated instrumentation, highly complex pipelines, and confined spaces. In addition, the floor area in a high-tech plant is large and frequently contains a channel through the ground floor to the second or third floor. This channel design enables the fire compartment to be destroyed. Therefore, the system cannot confine the fire to a specific area, thus hindering fire-relief operations. In this study, the original fire outbreak occurred in the PP processing area on the ground floor. The acetone storage tank was located on the third floor. The investigation conducted at the fire site of the situations of the burning (bursting) loss determined that the acetone liquid leaked and dripped from floor cracks and tunnel oven to the PP processing area. Because the PP manufacturing process rapidly generates static electricity, the flammable liquids made contact with the source of ignition, which caused the explosion and fire. Various procedures, such as those involving the operating environment of production, packaging, and processing in a high-tech plant, are likely to produce static electricity in a workplace. Improved electrostatic management can prevent the loss of property and lives, liquid acetone leakage, and loss of equipment caused by static electricity fire. (C) 2015 The Institution of Chemical Engineers. Published by Elsevier B.V. All rights reserved.
引用
收藏
页码:116 / 121
页数:6
相关论文
共 50 条
  • [1] EXPLOSION AND FIRE ENDANGER FROM STATIC ELECTRICITY IN CHEMICAL INDUSTRY FACTORIES
    SKIBINSK.A
    PRZEMYSL CHEMICZNY, 1970, 49 (02): : 64 - &
  • [2] Investigation into an explosion and fire in a mononitrotoluene manufacturing plant
    Cutler, DP
    Brown, AK
    JOURNAL OF HAZARDOUS MATERIALS, 1996, 46 (2-3) : 169 - 183
  • [4] Reaction characteristics of asphalt-salts mixture which caused a fire and explosion accident
    Sun, JH
    Hasegawa, K
    THEORY AND PRACTICE OF ENERGETIC MATERIALS, VOL 5, PARTS A AND B, 2003, : 650 - 655
  • [5] Fire hazards of static electricity
    Clark, RM
    INDUSTRIAL AND ENGINEERING CHEMISTRY, 1925, 17 : 1127 - 1129
  • [6] A new insight into the accident investigation: A case study of Tianjin Port fire and explosion in China
    Zhou Aitao
    Fan Lingpeng
    PROCESS SAFETY PROGRESS, 2017, 36 (04) : 362 - 367
  • [7] Investigation of the Transfer Rate of Radioactive Materials in a Hydrogen Explosion Accident at a Reprocessing Plant
    Tamauchi, Yoshikazu
    Kodama, Takashi
    Sato, Naoya
    Saito, Keita
    Chikazawa, Takahiro
    NUCLEAR TECHNOLOGY, 2023, 209 (04) : 622 - 635
  • [8] Investigation of a refinery fire and explosion
    Le May, I
    PRESSURE EQUIPMENT TECHNOLOGY: THEORY AND PRACTICE, 2003, : 215 - 224
  • [9] A preliminary research into mechanism of explosion and fire accident of LPG
    Li, GS
    Yu, CM
    PROGRESS IN SAFETY SCIENCE AND TECHNOLOGY, VOL II, PT A AND B, 2000, 2 : 591 - 596
  • [10] Fire damp explosion accident model and dynamic simulation
    Miao, DJ
    Cheng, WM
    Sui, XH
    Miao, FT
    Wang, G
    PROGRESS IN SAFETY SCIENCE AND TECHNOLOGY, VOL V, PTS A AND B, 2005, 5 : 1228 - 1232