Decoupling Predictive Control of Reheat Steam Temperature of USC Double Reheat Unit

被引:0
|
作者
Su Rongqiang [1 ]
Shi Zhiliang [1 ]
Xie Kai [1 ]
机构
[1] NR Elect Co Ltd, Nanjing 211102, Peoples R China
关键词
double reheat unit; reheat steam temperature; decoupling predictive control; unit load test; better performance;
D O I
10.1109/ccdc.2019.8832980
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
Based on the actual operating results of the domestic and foreign USC(ultra-supercritical) double reheat units, the USC double reheat unit has better economic and environmental benefits than one reheat unit when they have same capacity. However, the reheat steam temperature of double reheat unit becomes a multivariable system which is characterized by strong coupling, big inertia, and time delay, due to the complexity and particularity of double reheat unit's boiler construction. Realizing the effective control of two reheat steam temperatures requires a prompt solution. Predictive control is an effective method against such characteristics as time delay and big inertia-controlled object. This paper presents a decoupling predictive control strategy with input constraints to control the reheat steam temperature. To measure the control quality of the reheat steam temperature control strategy, the increasing and decreasing load tests were analyzed on the emulation platform of 1000MW USC double reheat unit, using Xi'an Thermal Power Research Institute adopting APROS emulation software. Simulation results show that the decoupling predictive control strategy with input constraints can achieve a better performance (except disturbance rejection) when compared with PID (Proportion Integration Differentiation).
引用
收藏
页码:2530 / 2534
页数:5
相关论文
共 50 条
  • [1] Analysis of Gas Recirculation Influencing Factors of a Double Reheat 1000 MW Unit with the Reheat Steam Temperature under Control
    Yue, Meng
    Ma, Guoqian
    Shi, Yuetao
    ENERGIES, 2020, 13 (16)
  • [2] Enhancing peak shaving capability by optimizing reheat-steam temperature control of a double-reheat boiler
    Wang, Chaoyang
    Qiao, Yongqiang
    Liu, Ming
    Zhao, Yongliang
    Yan, Junjie
    APPLIED ENERGY, 2020, 260
  • [3] Cascade Active Disturbance Rejection Predictive Control for Superheated Steam Temperature of Ultra-supercritical Double-reheat Unit
    Sun M.
    Dong Z.
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2019, 39 (18): : 5415 - 5423
  • [4] Performance Analysis of Reheat Steam Temperature Control System of Thermal Power Unit Based on Constrained Predictive Control
    Li, Xiaoli
    Liu, Jian
    Wang, Kang
    Wang, Fuqiang
    Li, Yang
    COMPLEXITY, 2019, 2019
  • [6] OPTIMUM DESIGN OF A DOUBLE REHEAT STEAM SYSTEM IN AN ULTRA SUPERCRITICAL UNIT
    Zhou, Luyao
    Xu, Gang
    Xu, Cheng
    Yang, Yongping
    Li, Yuanyuan
    Deng, Jianling
    PROCEEDINGS OF THE ASME TURBO EXPO: TURBINE TECHNICAL CONFERENCE AND EXPOSITION, 2013, VOL 5B, 2013,
  • [7] Pressure Drop Optimization of the Main Steam and Reheat Steam System of a 1000 MW Secondary Reheat Unit
    Li, Yanfeng
    Liu, Jingru
    Huang, Guohe
    ENERGIES, 2022, 15 (09)
  • [8] Active disturbance rejection control for the reheated steam temperature of a double-reheat boiler
    Dai, Chengbo
    Xue, Yali
    Wu, Zhenlong
    Yan, Gangyao
    Li, Donghai
    Li, Zheng
    JOURNAL OF PROCESS CONTROL, 2023, 130
  • [9] SOME PROBLEMS IN CONTROL OF STEAM REHEAT
    REZNIK, VI
    SHLEIFER, BM
    ZARAISKII, SI
    THERMAL ENGINEERING, 1977, 24 (03) : 8 - 12
  • [10] Revealing steam temperature characteristics for a double-reheat unit under coal calorific value variation
    Zhu, Hengyi
    Tan, Peng
    He, Ziqian
    Ma, Lun
    Zhang, Cheng
    Fang, Qingyan
    Chen, Gang
    ENERGY, 2023, 283