Discrete model-based operation of cooling tower based on statistical analysis

被引:21
|
作者
Wang, Jian-Guo [1 ]
Shieh, Shyan-Shu [2 ]
Jang, Shi-Shang [3 ]
Wu, Chan-Wei [4 ]
机构
[1] Shanghai Univ, Shanghai Key Lab Power Stn Automat Technol, Sch Mechatron Engn & Automat, Shanghai 200072, Peoples R China
[2] Chang Jung Christian Univ, Dept Occupat Safety & Hlth, Tainan 71101, Taiwan
[3] Natl Tsing Hua Univ, Dept Chem Engn, Hsinchu 30013, Taiwan
[4] China Steel Corp, Energy & Air Pollut Control Sect, New Mat R&D Dept, Kaohsiung 81233, Taiwan
关键词
Statistical analysis; Cooling capability index; Model-based operation; Cooling tower; Energy conservation; PERFORMANCE EVALUATION; PREDICTION; DESIGN; MERKEL;
D O I
10.1016/j.enconman.2013.04.025
中图分类号
O414.1 [热力学];
学科分类号
摘要
This study is aimed to utilize the operation data to build a physical-meaningful and precise-enough model to assist the operation of a cooling tower. To do so, this work introduces a dimensionless index, which can describe the cooling capability of a cooling tower in terms of effective power utilization. In the first phase of this study, principal component analysis, one of factor analysis methods, is used to investigate effects of ambient air temperature and relative humidity on the cooling capability of a cooling tower. Based on the proposed cooling capability index, the operation data are partitioned into different groups by the fuzzy c-mean clustering algorithm. The resulted groups are distinctly categorized by the conditions of ambient air temperature and relative humidity. In the second phase of the study, data within the same mode of a set of fans are partitioned by the fuzzy c-mean clustering algorithm. The resulted groups of data are then modeled by linear regression. The acquired multiple models are highly accurate in predicting the output temperature of cooling water from the cooling tower. The acquired models assist the operator to accurately select the proper fan mode when process conditions, e.g., cooling loading, or environment conditions, e.g., ambient air temperature, change. It results in electricity saving. This study is concluded by the presentation of a discrete model-based approach to determine the fan mode. The application to a real cooling tower in an iron and steel plant is promising in saving electricity consumed by the fan set. (C) 2013 Elsevier Ltd. All rights reserved.
引用
收藏
页码:226 / 233
页数:8
相关论文
共 50 条
  • [1] Model-based optimal operation of heating tower heat pump systems
    Huang, Shifang
    Lu, Xing
    Zuo, Wangda
    Zhang, Xiaosong
    Liang, Caihua
    BUILDING AND ENVIRONMENT, 2019, 160
  • [2] Optimal Model-based Control of Chiller Tower Fan and Cooling Water Pump
    Qureshi, O. A.
    Javed, H.
    Afshari, A.
    Armstrong, P. R.
    ASHRAE TRANSACTIONS 2014, VOL 120, PT 2, 2014, 120
  • [3] DISCRETE-TIME MODEL-BASED SLIDING MODE CONTROLLERS FOR TOWER CRANE SYSTEMS
    Borlea, Anamaria-Ioana
    Precup, Radu-Emil
    Roman, Raul-Cristian
    FACTA UNIVERSITATIS-SERIES MECHANICAL ENGINEERING, 2023, 21 (01) : 1 - 20
  • [4] Model-based reasoning techniques for the analysis of protection operation
    Davidson, EM
    McArthur, SDJ
    McDonald, JR
    ENGINEERING INTELLIGENT SYSTEMS FOR ELECTRICAL ENGINEERING AND COMMUNICATIONS, 2005, 13 (02): : 97 - 103
  • [5] STATISTICAL MODEL-BASED ALGORITHMS FOR IMAGE-ANALYSIS
    THERRIEN, CW
    QUATIERI, TF
    DUDGEON, DE
    PROCEEDINGS OF THE IEEE, 1986, 74 (04) : 532 - 551
  • [6] MODEL-BASED STATISTICAL ANALYSIS OF POLSAR DATA.
    Eltoft, Torbjorn
    Doulgeris, Anthony
    Anfinsen, Stian N.
    2009 IEEE INTERNATIONAL GEOSCIENCE AND REMOTE SENSING SYMPOSIUM, VOLS 1-5, 2009, : 2257 - 2260
  • [7] Statistical model-based approaches to audio restoration and analysis
    Godsill, SJ
    Wolfe, PJ
    Fong, WNW
    JOURNAL OF NEW MUSIC RESEARCH, 2001, 30 (04) : 323 - 338
  • [8] Data Center Cooling Management and Analysis - A Model-Based Approach
    Zhou, Rongliang
    Wang, Zhikui
    Bash, Cullen E.
    McReynolds, Alan
    2012 28TH ANNUAL IEEE SEMICONDUCTOR THERMAL MEASUREMENT AND MANAGEMENT SYMPOSIUM (SEMI-THERM), 2012, : 98 - 103
  • [9] Model-based design and analysis of glucose isomerization process operation
    Papadakis, Emmanouil
    Pedersen, Sven
    Tula, Anjan K.
    Fedorova, Marina
    Woodley, John M.
    Gani, Rafiqul
    COMPUTERS & CHEMICAL ENGINEERING, 2017, 98 : 128 - 142
  • [10] Graduate courses in statistical and model-based analysis of physiological data
    Moore, Leon C.
    Solomon, Irene C.
    Clausen, Chris
    FASEB JOURNAL, 2008, 22