High-Frequency Model of Magnetic Rings for Simulation of VFTO Damping in Gas-Insulated Switchgear With Full-Scale Validation

被引:19
|
作者
Szewczyk, Marcin [1 ]
Pawlowski, Jaroslaw [2 ]
Kutorasinski, Kamil [2 ]
Piasecki, Wojciech [1 ]
Florkowski, Marek [1 ]
Straumann, Ulrich [3 ]
机构
[1] ABB Corp Res Ctr, PL-31038 Krakow, Poland
[2] AGH Univ Sci & Technol, Fac Phys & Appl Comp Sci, PL-30059 Krakow, Poland
[3] ABB Switzerland Ltd, CH-8050 Zurich, Switzerland
关键词
Attenuation; damping; disconnector switch; gas-insulated switchgear (GIS); magnetic ring; switching; transients; very fast transient overvoltages (VFTOs); FAST TRANSIENTS; GIS;
D O I
10.1109/TPWRD.2015.2417675
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Nanocrystalline magnetic rings have been experimentally proven for effective damping of very fast transient overvoltages (VFTOs) in gas-insulated switchgear (GIS). The application of any damping solution in a specific GIS setup (rated voltage, GIS arrangement) requires simulation-based design, which, in turn, requires reliable models with proven accuracy in demanding high-frequency and high-current VFTO conditions. This paper presents a new model of a magnetic ring, employing full frequency-dependent characteristics of the ring's complex impedance, as well as the dedicated approach on modeling the saturation effect of the material magnetization characteristics. The saturation effect is modeled by a bypassing branch, activated at a certain saturation current value calculated according to the specific magnetic material properties and for the VFTO main frequency component. The model was implemented in Electromagnetic Transients Program simulation software and validated experimentally in a full-scale 550-kV GIS test setup. The validation proved the applicability of the model for the assessment of VFTO damping effectiveness with the use of nanocrystalline magnetic rings and, thus, for the design of a particular magnetic-based damping solution in a specific GIS setting.
引用
收藏
页码:2331 / 2338
页数:8
相关论文
共 32 条
  • [1] Damping of VFTO in Gas-Insulated Switchgear by a New Coating Material
    Szewczyk, Marcin
    Piasecki, Wojciech
    Stosur, Mariusz
    Florkowski, Marek
    Riechert, Uwe
    IEEE TRANSACTIONS ON POWER DELIVERY, 2016, 31 (06) : 2553 - 2558
  • [2] Scale model of overheat failure in gas-insulated switchgear bus contact
    Li, Hongtao, 2014, Chinese Society for Electrical Engineering (34):
  • [3] Modeling of gas-insulated shunt reactor for high-frequency surge analysis
    Okabe, S
    Koutou, M
    Teranishi, T
    Ishikawa, M
    Kobayashi, T
    Saida, T
    ELECTRICAL ENGINEERING IN JAPAN, 1998, 123 (02) : 32 - 39
  • [4] Modeling of gas-insulated shunt reactor for high-frequency surge analysis
    Tokyo Electric Power Co, Inc, Tokyo, Japan
    Electr Eng Jpn, 2 (32-39):
  • [5] Requirements for ultra-high frequency partial discharge monitoring systems for gas-insulated switchgear
    Koltunowicz, Wojciech
    Behrmann, Glenn
    Boltze, Matthias
    Caprara, Andrea
    Coapes, Graeme
    Cook, Fraser
    Hama, Hiroyuki
    Huecker, Thomas
    Johnstone, Carl
    Neuhold, Stefan
    Neumann, Claus
    Ohtsuka, Shinya
    Penning, Jean-Francois
    Riechert, Uwe
    Rokunohe, Toshiaki
    Schichler, Uwe
    Soeller, Markus
    Yasouka, Takanori
    ELEKTROTECHNIK UND INFORMATIONSTECHNIK, 2023, 140 (01): : 153 - 161
  • [6] Requirements for ultra-high frequency partial discharge monitoring systems for gas-insulated switchgear
    Wojciech Koltunowicz
    Glenn Behrmann
    Matthias Boltze
    Andrea Caprara
    Graeme Coapes
    Fraser Cook
    Hiroyuki Hama
    Thomas Huecker
    Carl Johnstone
    Stefan Neuhold
    Claus Neumann
    Shinya Ohtsuka
    Jean-Francois Penning
    Uwe Riechert
    Toshiaki Rokunohe
    Uwe Schichler
    Markus Soeller
    Takanori Yasouka
    e & i Elektrotechnik und Informationstechnik, 2023, 140 : 153 - 161
  • [7] A Novel Arc Model for Very Fast Transient Overvoltage Simulation in a 252-kV Gas-Insulated Switchgear
    Zhan, Huamao
    Duan, Shaofeng
    Li, Chengrong
    Yao, Linzhi
    Zhao, Lin
    IEEE TRANSACTIONS ON PLASMA SCIENCE, 2014, 42 (10) : 3423 - 3429
  • [8] Identification of ultra-high-frequency PD signals in gas-insulated switchgear based on moment features considering electromagnetic mode
    Bin, Feng
    Wang, Feng
    Sun, Qiuqin
    Chen, She
    Fan, Jingmin
    Ye, Huisheng
    HIGH VOLTAGE, 2020, 5 (06) : 688 - 696
  • [9] One-Shot Learning for Partial Discharge Diagnosis Using Ultra-High-Frequency Sensor in Gas-Insulated Switchgear
    Tuyet-Doan, Vo-Nguyen
    Do, The-Duong
    Tran-Thi, Ngoc-Diem
    Youn, Young-Woo
    Kim, Yong-Hwa
    SENSORS, 2020, 20 (19) : 1 - 13
  • [10] Dielectric properties of SF6/N2 gas mixtures on a full scale model of the gas-insulated busbar
    Hoshina, Y
    Sato, M
    Murase, H
    Toyoda, M
    Kobayashi, A
    2000 IEEE POWER ENGINEERING SOCIETY WINTER MEETING - VOLS 1-4, CONFERENCE PROCEEDINGS, 2000, : 2129 - 2134