Energy and exergy analyses of an experimental open-cycle desiccant cooling system

被引:146
|
作者
Kanoglu, M [1 ]
Carpinlioglu, MÖ [1 ]
Yildirim, M [1 ]
机构
[1] Gaziantep Univ, Dept Mech Engn, TR-27310 Gaziantep, Turkey
关键词
desiccant cooling systems; dehumidifier; desiccant; air-conditioning; heat driven cycle;
D O I
10.1016/j.applthermaleng.2003.10.003
中图分类号
O414.1 [热力学];
学科分类号
摘要
A procedure is developed for the energy and exergy analyses of open-cycle desiccant cooling systems and it is applied to an experimental unit operating in ventilation mode with natural zeolite as the desiccant. The same procedure and formulations may easily be applied to the units operating in recirculation mode. Energy-based performance parameters such as the coefficient of performance (COP) of the unit and the effectiveness' of system components are presented. Exergy destruction and exergy efficiency relations for the system and its components as well as the reversible COP of the system are derived. The energy and exergy formulations are applied to the experimental unit using the data collected during a typical operation of the unit. The unit has a COP of 0.35, a reversible COP of 3.11, and an exergy efficiency of 11.1%. Desiccant wheel has the greatest percentage of total exergy destruction with 33.8% followed by the heating system with 31.2%. Rotary regenerator and evaporative coolers account for the remaining exergy destructions. The analysis shows that an exergy analysis can provide useful information with respect to the theoretical upper limit of the system performance, which cannot be obtained from an energy analysis alone. The analysis allows us to identify and quantify the sites with the losses of exergy, and therefore showing the direction for the minimization of exergy losses to approach the reversible COP. (C) 2003 Elsevier Ltd. All rights reserved.
引用
收藏
页码:919 / 932
页数:14
相关论文
共 50 条
  • [1] PERFORMANCE OF AN OPEN-CYCLE DESICCANT COOLING SYSTEM USING ADVANCED DESICCANT MATRICES
    MAJUMDAR, P
    WOREK, WM
    HEAT RECOVERY SYSTEMS & CHP, 1989, 9 (04): : 299 - 311
  • [2] PARAMETRIC STUDY OF AN OPEN-CYCLE ADIABATIC, SOLID, DESICCANT COOLING SYSTEM
    CHAROENSUPAYA, D
    WOREK, WM
    ENERGY, 1988, 13 (09) : 739 - 747
  • [3] AN OVERVIEW OF OPEN-CYCLE DESICCANT-COOLING SYSTEMS AND MATERIALS
    COLLIER, RK
    BARLOW, RS
    ARNOLD, FH
    JOURNAL OF SOLAR ENERGY ENGINEERING-TRANSACTIONS OF THE ASME, 1982, 104 (01): : 28 - 34
  • [4] PERFORMANCE ANALYSIS OF AN OPEN-CYCLE LIQUID DESICCANT COOLING SYSTEM USING SOLAR-ENERGY FOR REGENERATION
    GANDHIDASAN, P
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1994, 17 (07): : 475 - 480
  • [5] THE PERFORMANCE OF A SOLAR-REGENERATED OPEN-CYCLE DESICCANT BED GRAIN COOLING SYSTEM
    ISMAIL, MZ
    ANGUS, DE
    THORPE, GR
    SOLAR ENERGY, 1991, 46 (02) : 63 - 70
  • [6] PERFORMANCE STUDIES FOR AN EXPERIMENTAL SOLAR OPEN-CYCLE LIQUID DESICCANT AIR DEHUMIDIFICATION SYSTEM
    PATNAIK, S
    LENZ, TG
    LOF, GOG
    SOLAR ENERGY, 1990, 44 (03) : 123 - 135
  • [7] Effect of irreversible processes on the thermodynamic performance of open-cycle desiccant cooling cycles
    La, Dong
    Li, Yong
    Dai, Yanjun
    Ge, Tianshu
    Wang, Ruzhu
    ENERGY CONVERSION AND MANAGEMENT, 2013, 67 : 44 - 56
  • [8] Control design of open-cycle desiccant cooling systems using a graphical environment tool
    Ginestet, S.
    Stabat, P.
    Marchio, D.
    Building Services Engineering Research and Technology, 2004, 24 (04) : 257 - 269
  • [9] EFFECT OF ADSORBENT HEAT AND MASS-TRANSFER RESISTANCES ON PERFORMANCE OF AN OPEN-CYCLE ADIABATIC DESICCANT COOLING SYSTEM
    CHAROENSUPAYA, D
    WOREK, WM
    HEAT RECOVERY SYSTEMS & CHP, 1988, 8 (06): : 537 - 548
  • [10] Theoretical analysis of an open-cycle absorption heating and cooling system
    Lazzarin, R.M.
    Longo, G.A.
    Gasparella, A.
    International Journal of Refrigeration, 1996, 19 (03): : 160 - 167