Steady-state stability analysis of doubly-fed induction generators under decoupled P-Q control

被引:33
作者
Banakar, H [1 ]
Luo, C [1 ]
Ooi, BT [1 ]
机构
[1] McGill Univ, ECE Dept, Montreal, PQ H3A 2A7, Canada
来源
IEE PROCEEDINGS-ELECTRIC POWER APPLICATIONS | 2006年 / 153卷 / 02期
关键词
D O I
10.1049/ip-epa:20050388
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Based on the standard mathematical model of the doubly-fed induction generator (DFIG) and steady-state stability analysis, DFIGs operating under decoupled P-Q control and maintaining fixed real power outputs are expected to be unstable. Yet actual field experiences suggest to the contrary. The research presented here resolves this contradiction and confirms that DFIGs have extensive steady-state stability regions. The research reveals, for the first time, that a DFIG's stable region is bounded by unstable regions on both the low- and high-speed ends. The eigenvalue predictions of the unstable regions have been confirmed by simulations.
引用
收藏
页码:300 / 306
页数:7
相关论文
共 13 条
[1]  
AKAGI H, 2002, IEEE T POWER ELECT, V17
[2]  
Datta R., 2001, IEEE T IND ELECT, V48
[3]   STEADY-STATE OSCILLATION AND STABILISATION OF VARIABLE-FREQUENCY INVERTOR-FED INDUCTION-MOTOR DRIVES [J].
FALLSIDE, F ;
WORTLEY, AT .
PROCEEDINGS OF THE INSTITUTION OF ELECTRICAL ENGINEERS-LONDON, 1969, 116 (06) :991-+
[4]  
Hofmann W., 2001, P 4 IEEE INT C POW E, V1, P355
[5]  
Krause C., 1986, ANAL ELECT MACHINERY
[6]   Double-fed induction machine: converter optimisation and field oriented control without position sensor [J].
Morel, L ;
Godfroid, H ;
Mirzaian, A ;
Kauffmann, JM .
IEE PROCEEDINGS-ELECTRIC POWER APPLICATIONS, 1998, 145 (04) :360-368
[7]   Doubly fed induction generator systems for wind turbines [J].
Müller, S ;
Deicke, M ;
De Doncker, RW .
IEEE INDUSTRY APPLICATIONS MAGAZINE, 2002, 8 (03) :26-33
[8]  
MULLER S, IAS 2000 C REC, V4, P2249
[9]  
NELSON RH, 1969, IEEE T POWER AP SYST, VPA88, P1710, DOI 10.1109/TPAS.1969.292379
[10]  
OOI BT, 1972, IEEE WINT M JAN 30 F